2002-08-22 00:00:00 | ************* UNSAT ****************** |
| |
| 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| IN THE VICINITY OF BEDROOMS AND CLOSE |
| PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| |
| 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S). PER 210-11-C-3 |
| MUST BE 20A AND #12AWG. |
| PLEASE NOTE MISSING REQ`D RECEPTS IN |
| MANY BATHS REQ`D PER 210-52D |
| |
| 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210-8-A-6. |
| INCLUDES KITCHEN ISLANDS. |
| |
| 4)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| KITCHEN OUTLETS TO MEET 210-52-C,1,2,3, |
| ,4,5. |
| |
| 5)NOTE: PLEASE NOTE MISSING EGRESS |
| LIGHTING PER 210-70, HALLWAY ETC. |
| |
| 6) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| |
| 7))NOTE: PLEASE LIST THE REQ`D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| CIRCUIT PROTECTION. PER 210-12 |
| |
| 8)NOTE: PLEASE SHOW LOCATION OF EXISTING |
| PANELS. |
| PLEASE SUBMIT PANEL SCHEDULES. |
| |
| PLEASE NOTE THAT NO HANDWRITTEN CHANGES |
| MAY BE ON PLANS, UNLESS EACH CHANGE IS |
| SIGNED AND DATED BY THE ARCH OF RECORD. |
| FS/FAC 481.221. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |