2002-08-22 00:00:00************* UNSAT ******************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
 PLEASE NOTE MISSING REQ`D RECEPTS IN
 MANY BATHS REQ`D PER 210-52D
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 4)NOTE: PLEASE NOTE OUTLET SPACING FOR
 KITCHEN OUTLETS TO MEET 210-52-C,1,2,3,
 ,4,5.
  
 5)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING PER 210-70, HALLWAY ETC.
  
 6) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 7))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 8)NOTE: PLEASE SHOW LOCATION OF EXISTING
 PANELS.
 PLEASE SUBMIT PANEL SCHEDULES.
  
 PLEASE NOTE THAT NO HANDWRITTEN CHANGES
 MAY BE ON PLANS, UNLESS EACH CHANGE IS
 SIGNED AND DATED BY THE ARCH OF RECORD.
 FS/FAC 481.221.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  