2002-08-22 00:00:00 | SHEET 4 OF 5.IF THE TERM "INSTALL | | CONTACTS ON DOORS" IS INTENDED TO BE A | | HOLD OPEN DEVICE FOR THE STAIR SHAFT | | DOORS, PROVIDE SPECIFIC DESIGN | | INFORMATION DEMONSTRATING COMPLIANCE | | WITH FBC 705.1.3.2.3 AND THE APPLICABLE | | PORTIONS OF FBC 1012.1.11. ALSO, PROVIDE | | DOCUMENTATION THAT THE LISTING FOR THE | | EXISTING DOOR MAY BE ALTERED IN THIS | | FASHION | | | | WHAT CONTROLS OR PRECAUTIONS FOR THE | | CUTTING OF THE STRUCTURAL FLOOR SLAB, | | IF ANY, ARE TO BE TAKEN?DOES THE | | ARCHITECT HAVE KNOWLEDGE OF THE | | EXISTING CONDITIONS?SEE FBC 104.2.3. | | | | SHOW THE FIRE PROTECTION, (SPRINKLERS & | | ALARM) DESIGN ALTERATION ON THE PLANS. | | SEE FBC 104.3.1 |
|