2002-08-22 00:00:00SHEET 4 OF 5.IF THE TERM "INSTALL
 CONTACTS ON DOORS" IS INTENDED TO BE A
 HOLD OPEN DEVICE FOR THE STAIR SHAFT
 DOORS, PROVIDE SPECIFIC DESIGN
 INFORMATION DEMONSTRATING COMPLIANCE
 WITH FBC 705.1.3.2.3 AND THE APPLICABLE
 PORTIONS OF FBC 1012.1.11. ALSO, PROVIDE
 DOCUMENTATION THAT THE LISTING FOR THE
 EXISTING DOOR MAY BE ALTERED IN THIS
 FASHION
  
 WHAT CONTROLS OR PRECAUTIONS FOR THE
 CUTTING OF THE STRUCTURAL FLOOR SLAB,
 IF ANY, ARE TO BE TAKEN?DOES THE
 ARCHITECT HAVE KNOWLEDGE OF THE
 EXISTING CONDITIONS?SEE FBC 104.2.3.
  
 SHOW THE FIRE PROTECTION, (SPRINKLERS &
 ALARM) DESIGN ALTERATION ON THE PLANS.
 SEE FBC 104.3.1