2002-09-06 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PROVIDE UPDATED SURVEY WITH CORRECT |
| STREET NAMES. |
| |
| 3) INDICATE THE APPROPRIATE INTERNAL |
| PRESSURE COEFFICIENT ON THE PLANS AS |
| REQUIRED BY 2001 FBC 1606.1.7. |
| |
| 4) PROVIDE UL LISTING AND MANUFACTURER'S |
| SPECIFICATIONS FOR ONE HOUR RATED GLASS |
| BLOCK ASSEMBLY, WHICH IS REQUIRED AT |
| ZERO LOT LINE. |
| |
| 5) INDICATE THE LOCATION AND MATERIAL |
| USED FOR THE FLOOR/CEILING DRAFTSTOPPING |
| PER 2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| ING ASSEMBLIES SEPERATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. |
| |
| 6) INDICATE THE ACCESS TO ATTIC SPACE AT |
| THE GARAGE AND COVERED PORCH, IF THE |
| CLEAR HEIGHT OF THE ATTIC SPACE AT THE |
| PEAK IS 24" OR MORE. SEE FBC 2309.6 |
| |
| 7) PLEASE CLARIFY THE SH24E WINDOW SIZE |
| AT THE SECOND FLOOR BEDROOMS. ARE THESE |
| THE SAME AS A SH24-5 (37"X56")? SEE |
| FBC 1005.4. |
| |
| 8) INDICATE FIRE BLOCKING AT THE STAIRS |
| AS REQUIRED BY FBC 2305.1.4 AT THE TOP |
| AND BOTTOM OF STAIR RUNS. |
| |
| 9) REVISE THE GARAGE DOOR BUCK DETAIL TO |
| CONCUR WITH THE CONNECTION DETAILS |
| SPECIFIED IN THE PRODUCT APPROVAL ON |
| PAGE 3 OF THE DRAWINGS. |
| |
| 10) FBC 1707.4.4 REQUIRES WOOD BUCKS |
| 1-1/2" TO EXTEND BEYOND THE INTERIOR |
| FACE OF THE DOOR FRAME. PLEASE REVISE |
| THE EXTERIOR BUCK DETAIL ACCORDINGLY. |
| |
| 11) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - FRENCH DOOR AT CABANA BATH |
| - OVAL AND ARCHED TOP FIXED GLASS |
| |
| 12) PROVIDE DETAILS/SPECS. FOR CEILING |
| INSTALLATIONS AT ENTRY AND COVERED PORCH |
| SPECIFY THE CEILING MATERIAL THAT WILL |
| BE USED. SEE ASTM C 1063 FOR REQUIRED |
| FASTENERS AND METAL LATHE FOR STUCCO |
| APPLICATION. |
| |
| 13) SPECIFY CONCRETE SLAB CONTROL JOINTS |
| OR SPECIFY SUPPORTS FOR W.W.M. SEE FBC |
| 1909.3. |
| |
| 14) IF TAKING CEILING FAN CREDIT AS |
| INDICATED ON THE ENERGY CALCS., THEN |
| SPECIFY THE FAN SIZES ON THE PLANS,AS |
| REQUIRED BY TABLE 6-6 FBC CHAPTER 13. |
| |
| 15) ITEM #14 UNDER "SECTION & DETAILS |
| KEY NOTES" ON A-6 INDICATES THAT VENTS |
| ARE ONLY REQUIRED FOR ATTIC SPACE ABOVE |
| LIVING AREA. ALL ATTIC SPACE IS REQUIRED |
| TO BE VENTED PER 2001 FBC 1203.1.3 AND |
| 2309.6. PLEASE REVISE. |
| |
| 16) THE COLUMN SCHEDULE ON S-1 LISTS (3) |
| 2X4 AND S-2 HAS (2) 2X4 FOR COLUMN C2. |
| PLEASE CORRECT. |
| |
| 17) SPECIFY THE ANCHOR BOLT LENGTH AND |
| EMBEDDMENT FOR THE USP TD7 AT WOOD |
| COLUMN C2. |
| |
| 18) INDICATE THE FASTENERS AND SPACING |
| REQUIRED TO CONSTRUCT THE 2X4 WOOD |
| COLUMN (C2) AND THE 2X6 COLUMN UNDER THE |
| GIRDER TRUSSES ON THE SECOND FLOOR. |
| |
| 19) INDICATE THE STUD TO PLATE CONNECTOR |
| ON SECTION 3 ON S-1. |
| |
| 20) SECTION 4 ON S-1 IS NOT INDICATED ON |
| THE FOUNDATION PLAN ON S-1. |
| |
| 21) PLEASE CORRECT THE TYPOS AT SECTION |
| 6 ON S-1 ( ? AFTER 5/8" AND 1/2 BETWEEN |
| 1 AND 2. PROVIDE DETAIL OF THE STEEL |
| COLUMN CAPS. |
| |
| 22) PROVIDE DETAIL FOR THE ATTACHMENT OF |
| THE LOWER ROOF WOOD TRUSSES TO THE |
| MASONRY WALLS AT THE COVERED PORCH. |
| |
| 23) PROVIDE SIGNED AND SEALED ENGINEERED |
| DRAWINGS (REVIEWED AND APPROVED BY THE |
| ARCHITECT) FOR THE GIRDER TRUSS HANGER |
| SHOWN IN DETAIL D ON S-2. |
| |
| 24) PROVIDE DETAILS OF THE WOOD FRAME |
| BEARING WALLS CONNECTION TO THE FLOOR |
| GIRDER TRUSSES. (CONNECTOR TYPE, SPACING |
| ETC.) |
| |
| 25) SPECIFY THE LENGTH/EMBEDDMENT OF THE |
| 3/4" ANCHOR BOLTS FOR THE USC 53 ANCHOR |
| AT DETAIL F ON S-3. |
| |
| 26) PROVIDE DETAILS/SPECIFICATIONS FOR |
| WOOD FRAME SHEAR WALLS ON SECOND FLOOR. |
| INDICATE HOLDDOWNS, SHEATHING, FASTENER |
| TYPES, SPACING, ETC. |
| |
| 27) INDICATE NAILING REQUIREMENTS FOR |
| ROOF SHEATHING AT ZONES 1,2 & 3 PER CITY |
| OF W.P.B. AMENDMENTS TO THE 2001 FBC. |
| |
| 28) INDICATE THE NAILING REQUIREMENTS |
| FOR THE PLYWOOD FLOOR DIAPHRAGM. |
| |
| 29)PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. |
| |
| 30)FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| PROVIDE SOIL BEARING TEST REPORT. |
| |
| PLEASE RETURN BOTH SETS OF OLD PLAN |
| SHEETS WHEN RESUBMITTING NEW PLANS TO |
| EXPEDIATE PLAN REVIEW. |
| |