| BUILDING PLAN REVIEW |
| PERMIT: 02080924 |
| ADD:******LIBERTY BAY***** |
| ****MODEL "D"**** |
| CONT: HOME DYNAMICS CONSTRUCTION |
| TEL: (954)275-8569 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) SHEET A-2 NOTE: MONOLITHIC CONCRETE |
| FOUNDATION WITHOUT HOOK BARS DESIGNED |
| BY RATIONAL ANYLSIS PER ACI 318-89 |
| THE PLAN DOES NOT INDICATE AS TO THE |
| MINIMUM DEPTH REQUIRED? DETAI 3/1 GARAGE |
| SLAB, DOES THE VERTICAL DOWELS REQUIRE |
| ADDTIONAL LENGHT INTO THE CONCRETE TO |
| GET THE REQUIRED COVERAGE SINCE THERE |
| IS NO HOOK? |
| ACI 530 8.5.2 EMBEDDMENT LENGHT MIN 12". |
| |
| 2105.1 SHEAR WALLS. WHERE THE STRUCTURE |
| DEPENDS ON MASONARY WALLS FOR LATERAL |
| STABILITY, SHEAR WALLS SHEAR WALLS SHALL |
| BE PROVIDED TO THE DIRECTION OF THE |
| LATERAL FORCES RESISTED. DEMONSTRATE HOW |
| THE 2ND STORY FRAME WALLS WILL TRANSFER |
| THE WIND LOADS IF WIND IS AT 90 DEGREES |
| TO THE FRONT OR REAR OF BUILDING. THE |
| FRONT OF THE BUILDING IS BEING HELD |
| UP BY COLUMNS NO WALL SECTIONS TO TRANS- |
| FER SHEAR. |
| |
| 3) NO FLOOR DIAPHRAM INDICATED, 2310.3.1 |
| NOR IS THERE IN THE 2ND STORY FRAME |
| WALLS, TABLE 2310.2B PROVIDE ADDITIONAL |
| INFORMATION. |
| |
| 4) SHEET A-1 INDICATES WIND ZONE OF |
| 130 MPH, CORRECT TO 140 MPH. |
| |
| 5) SHEET A-4 MEAN ROOF HEIGHT < 25'. |
| ROOF SHEATHING NAILING REQUIREMENTS |
| ZONE 1 & 2 8D COMMONS |
| 6" EDGES & 6" INTERMEDIATES |
| ZONE 38D COMMONS |
| 4" EDGES & 6" INTERMEDIATES |
| |
| 6) PROVIDE KEY PLAN FOR INSTALLTION |
| SCHEDULE/ STORM SHUTTERS. |
| |
| 7) 1007.8.1 WINDERS SHALL HAVE A |
| MINIMUM TREAD DEPTH OF 6" AT THE NARROW- |
| EST EDGE & SHALL HAVE A MINIMUM TREAD |
| DEPTH OF 11" AT A POINT 12" FROM THE |
| NARROW EDGE. WINDERS SHALL BE PERMITTED |
| TO BE USED AS A COMPONENT IN MEANS OF |
| EGRESS WITHIN A DWELLING UNIT. SEE |
| DETAIL A-5. |