 BUILDING PLAN REVIEW
 PERMIT: 02080923
 ADD:****LIBERTY BAY****
 *****MODEL "C"****
 CONT: HOME DYNAMICS CONSTRUCTION
 TEL: (954)275-8569
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET A-1 NOTE: MONOLITHIC CONCRETE
 FOUNDATION WITHOUT HOOK BARS DESIGNED
 BY RATIONAL ANYLYSIS PER ACI318-89.
 THE PLAN DOES NOT INDICATE WHAT DEPTH
 THE BARS ARE TO BE EMBEDDED? ALSO ARE
 THE REBARS TO BE EPOXIED INTO THE SLAB?
 IF SO WHAT LENGHT?
 ACI 530 8.5.2 EMBEDDMENT LENGHT MIN 12".
 DETAIL 2/1 INDICATES WALL SEC THROUGH
 THE GARAGE, SINCE NO HOOK ON VERTICAL
 RODS, WILL THESE REBAR BE EMBEDDED AN
  
  
 2) 2105.1 SHEAR WALLS. WHERE THE STRUC-
 TURE DEPENDS ON MASONARY WALLS FOR LATER
 AL STABILITY, SHEAR WALLS SHALL BE PRO-
 VIDED PARELLEL TO THE DIRECTION OF THE
 LATERAL FORCES RESISTED. SHOW HOW THE
 2ND STORY FRAME STRUCTURE WILL BE TRANS-
 FERED TO THE FRONT OF THE BUILDING, WIND
 FROM THE SIDE PUSHING ONTO THE FRONT
 PORCH AREA, NO SHEAR WALL SEGMENTS, NO
 BLOCK WALLS ONLY MASONARY COLUMNS?
  
 3) NO FLOOR DIAPHRAM INDICATED,2310.3.1
 NOR IS THERE IN FORMATION ON 2ND STORY
 WOOD FRAME WALLS, HOW CONTINUOUS LOAD WI
 LL BE TRANSFERRED FROM THE ROOF THROUGH
 THE FRAME WALLS (TABLE 2310.2B) SHOW
 RATIONAL ANALYSIS, CALCULATIONS.
  
 4) SHEET A-3 BUILDING DATA, PLANS INDI-
 CATE THAT THEY ARE DESIGNED TO 130 MPH,
 REDESIGN FOR 140 MPH WIND ZONE. PROVIDE
 ADDITIONAL INFO FOR REDESIGN.
  
 5) SHEET A-3 MEAN ROOF HEIGHT < 25'
 ROOF SHEATHING NAILING REQUIREMENTS
 ZONES 1 & 28D COMMONS,
 6" O.C. EDGES & 6" O.C. INTERMEDIATES
 ZONE 38D COMMONS
 4" O.C. EDGES & 6" O.C. INTERMEDIATES
  
 6) IDENTIFY NAILING REQUIREMENTS FOR
 2ND STORY FRAME WALL SHEATHING, SEE
 TABLE 2310.2A.
  
 7) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4. **MISSING KEY PLAN**
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved