2002-10-28 00:00:00 | BUILDING PLAN REVIEW |
| ******PROVISO******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| --PROVISO-- |
| FBC 1606.1.4THE SUBMITTED MADDEN |
| IMPACT PROTECTION PANEL DRAWING (NUMBER |
| 28GAWC/3-2002/S) DOES NOT CORRESPOND TO |
| ITEM# 6 OF THE SUBMITTED SBCCI PRODUCT |
| APPROVAL REPORT# 2056 FOR MADDEN STORM |
| PANELS. SUBMIT TWO COPIES OF THE CORRECT |
| PRODUCT APPROVED MADDEN STORM PANEL |
| DRAWINGS LISTED UNDER THE ITEM# 6 |
| HEADING 'SUBSTANTIATING DATA', OR SUBMIT |
| AN ALTERNATIVE PRODUCT APPROVAL. |
| |
| --PROVISO-- |
| FBC 1504ROOF COVERINGS.THE SOUTH |
| ELEVATION SHOWS 'ROOF SHINGLE TO MATCH |
| EXISTING' OVER THE DEN, BUT THE |
| SUBMITTED PRODUCT APPROVAL IS FOR A FLAT |
| PROFILE CONCRETE ROOF TILE.BEFORE ROOF |
| SHEATHING INSPECTION, SUBMIT TWO COPIES |
| OF AN APPROPRIATE PRODUCT APPROVAL FOR |
| THE SPECIFIED ROOF COVERING TYPE.ALSO, |
| SHEETS 2,3,6,7 AND 8 OT THE SUBMITTED |
| TAMKO MODIFIED BITUMEN ROOF SYSTEM |
| PRODUCT APPROVAL NOA# 01-0509.01 ARE |
| EITHER MISSING OR IMPROPERLY COPIED. |
| SUBMIT TWO COPIES. |