2002-08-27 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 02080881 |
| ADD: 202 32ND STREET |
| CONT: WAYNE HETZEL BUILDING |
| TEL: (561)881-2108 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| |
| PROVIDE 2 CURRENT COPIES OF SIGNED & |
| SEALED SURVEYS WITH PROPOSED IMPROVEMENT |
| TO BE COMPLETED. PROPERTY IS LOCATED IN |
| FLOOD ZONE "A5", SURVEY TO INDICATE |
| THE FINISH FLOOR HEIGHT OF THE EXISTING |
| BUILDING, AND A/C PAD. |
| |
| PROVIDE FLOOD ZONE ELEVATION |
| CERTIFICATE FOR NEW CONSTRUTION WITH |
| BASE FLOOD ELEVATION, CITY CODE REQUIRES |
| AN ADDITIONAL 6". THE MINIMUM HEIGHT OF |
| THE NEW FINISH FLOOR ELEVATION OF THE |
| ADDITION IS 7'-6" NGVD. THE FLOOR LEVEL |
| OF THE EXISTING STRUCTURE SHALL ALSO BE |
| REQUIRED TO BE 7'-6" NGVD. SEE CITY CODE |
| 12-17 SUBSTANTIAL IMPROVEMENTS: MEANS |
| ANY COMBINATION OF REPAIRS, RECONSTRUC- |
| TION, ALTERATIONS OR IMPROVEMENTS TO A |
| STRUCTURE, TAKING PLACE DURING THE LIFE |
| OF THE STRUCTURE, IN WHICH THE CUMULA- |
| TIVE COST EQUALS OR EXCEEDS 50% OF THE |
| MARKET VALUE OF THE STRUCTURE. |
| |
| PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| TION. |
| |
| 1503.4.2 OVERFLOW DRAINS SHALL BE |
| THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| WITH THE INLET FLOW LINE LOCATED 2" |
| ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| OR PARARETS WITH THE INLET FLOW LINE |
| NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| |
| 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST OR STORM SHUTTERS MEET |
| ING SUCH TEST. |
| |
| PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. |
| |
| FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 1504.1 WIND RESISTANCE TO ROOFS. |
| PROVIDE PRODUCT TESTING FOR FLAT ROOF |
| ASSEMBLY. |
| |
| 1015.2 HEIGHT. GUARDRAILS SHALL |
| FORM A VERTICAL PROTECTIVE BARRIER NOT |
| LESS THAN 42" HIGH. |
| 1015.3 OPENINGS. OPEN GUARDRAILS |
| SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| REJECT THE PASSAGE OF 2" DIAMETER |
| SPHERE. |
| |
| 1608.2.3 THE GUARDRAIL SYSTEM SHALL |
| BE DESIGNED AND CONSTRUCTED TO RESIST A |
| 200 LB CONCENTRATED HORIZONTAL LOAD |
| APPLIED ON A 1 SQ FT AREA AT ANY POINT |
| IN THE SYSTEM INCLUDING INTERMEDIATE |
| RAILS OR OTHER ELEMENTS SERVING THIS |
| PURPOSE. SHOW ATTACHMENT DETAILS TO |
| PARAPET & DECK? |
| |
| 3401.7.2 WHERE AND EXISTING BUILD- |
| ING AND THE ADDITION ARE NOT SEPERATED |
| BY A FIRE WALL AND THE AREA OF THE ADDIT |
| ION IS IS 25% OR MORE OF THE AREA OF THE |
| EXISTING BUILDING, AND THE ADDITION |
| SHALL BE MADE TO COMPLY WITH ALL REQUIRE |
| MENTS OF THIS CODE FOR A BUILDING OF |
| AREA OF THE ADDITION & EXISTING BUILDING |
| EXCEPTION: EXISTING BUILDINGS SHALL NOT |
| BE REQUIRED TO BE UPGRADED TO THE STRUC- |
| TURAL REQUIREMENTS OF THE CODE IN EFFECT |
| ON THE DATE OF APPLICATION OF THE |
| PERMIT FOR THE ADDITION. |
| |
| BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |