Plan Review Notes For Permit 02080797
Permit Number 02080797
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-27 00:00:00************* PROVISO/NOTES **********
  
 1)NOTE: PLEASE NOTE EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN AND PANEL NOT
 SHOWN. SIZE PER 250-122
  
 2)NOTE: PLEASE NOTE WRONG ARTS FROM NEC
 ARE REFERENCED IN NOTES. THOSE ARTS ARE
 FROM THE 96 NEC. PLEASE CORRECT TO 99
 NEC.
  
 3)NOTE: PLEASE NOTE, NO INDICATION FOR
 REQ`D ARC FAULT PROTECTION PER 210-12.
 IT IS NOTED THAT RECEPTS ARE SHOWN W/
 A SLASH BUT NO INDICATION IS SHOWN ON
 SCHEDULE.
  
 4)NOTE: PLEASE NOTE AIC RATING SHOWN AS
 A MISPRINT AS 22.00, SHOULD BE 22,000.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -IONIS CALLED IN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372