Plan Review Notes
Plan Review Notes For Permit 02080795
Permit Number 02080795
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-27 00:00:00****************PROVISO/NOTE ***********
  
 1)NOTE: PLEASE NOTE MISSING ARC FAULT
 PROTECTION FOR BEDRROMS PER 210-12.
  
 2)NOTE: PLEASE NOTE, SD NEEDS TO BE
 MOVED IN MASTER HALLWAY TO MASTER
 BEDROOM. NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE NOTE SERVICE CONDUCTOR
 SIZE NEEDS TO BE SIZED PER 310-15/310-16
 SHOWN AS #2?
  
 4)NOTE: PLEASE NOTE ELECTRICAL IN
 MASTER BATH TO MOVE OVER.
  
 5)NOTE: PLEASE NOTE OUTLETS FOR KITCHEN
 ISLAND NEED TO BE CLARIFIED. PER 210-52-
 -C-3. GFI PROTECTION REQ`D PER 210-8-A-6
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372