Notes |
Date |
Text |
2002-08-27 00:00:00 | ************* PROVISO/REVISION ********* | | | | PLEASE NOTE ITEMS REDLINED ON PLANS FOR | | CORRECTIONS TO BE MADE. | | | | 1)NOTE: PLEASE NOTE WRONG CODE ARTS | | REFERENCED FROM "96" NEC. SHOULD BE | | 110-26,250-66,250-140. | | | | 2)NOTE: PLEASE NOTE AIC RATING SHOWN AS | | 22.00, SHOULD BE 22,000. | | | | 3)NOTE: PLEASE NOTE THAT THERE IS NO | | REFERENCE TO THE ARC FAULT PROTECTION | | REQUIRED BY 210-12. RECEPTS ARE SHOWN | | BEING DIFFERENT , BUT NOT DETAILED ON | | SCHEDULE. | | | | 4)NOTE: PLEASE NOTE MISSING EQUIPMENT | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | PANEL. SIZE PER 250-122 | | | | PLEASE SUBMIT THE ABOVE INFORMATION AS | | A REVSION BEFORE ROUGH INSPECTION IS | | CALLED IN. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|