Plan Review Notes
Plan Review Notes For Permit 02080793
Permit Number 02080793
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-27 00:00:00************* PROVISO/REVISION *********
  
 PLEASE NOTE ITEMS REDLINED ON PLANS FOR
 CORRECTIONS TO BE MADE.
  
 1)NOTE: PLEASE NOTE WRONG CODE ARTS
 REFERENCED FROM "96" NEC. SHOULD BE
 110-26,250-66,250-140.
  
 2)NOTE: PLEASE NOTE AIC RATING SHOWN AS
 22.00, SHOULD BE 22,000.
  
 3)NOTE: PLEASE NOTE THAT THERE IS NO
 REFERENCE TO THE ARC FAULT PROTECTION
 REQUIRED BY 210-12. RECEPTS ARE SHOWN
 BEING DIFFERENT , BUT NOT DETAILED ON
 SCHEDULE.
  
 4)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION AS
 A REVSION BEFORE ROUGH INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  