Plan Review Notes
Plan Review Notes For Permit 02080648
Permit Number 02080648
Review Stop FS
Sequence Number 1
Notes
Date Text
2002-08-21 00:00:001) NO FIRE DEPARTMENT CONNECTION SHOWN
 ON DRAWINGS. PLEASE PROVIDE A FIRE
 DEPARTMENT CONNECTION WITHIN 150 FEET
 OF A FIRE HYDRANT.
  
 2) UNDERGROUND PIPING TO BE RESTRAINED
 IN ACCORDANCE WITH NFPA 24.
  
 3) ALL UNDERGROUND PIPING TO BE PRESSURE
 TESTED AT 200 PSI FOR TWO HOURS.
  
 4) FIRE LINES ARE NOT ALLOWED TO BE RUN
 UNDERNEATH THE BUILDING UNLESS
 ABSOLUTLEY NECESSARY. PLEASE CLARIFY
 AND REVISE PLANS AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497