Plan Review Notes For Permit 02080648 |
Permit Number |
02080648 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-21 00:00:00 | 1) NO FIRE DEPARTMENT CONNECTION SHOWN | | ON DRAWINGS. PLEASE PROVIDE A FIRE | | DEPARTMENT CONNECTION WITHIN 150 FEET | | OF A FIRE HYDRANT. | | | | 2) UNDERGROUND PIPING TO BE RESTRAINED | | IN ACCORDANCE WITH NFPA 24. | | | | 3) ALL UNDERGROUND PIPING TO BE PRESSURE | | TESTED AT 200 PSI FOR TWO HOURS. | | | | 4) FIRE LINES ARE NOT ALLOWED TO BE RUN | | UNDERNEATH THE BUILDING UNLESS | | ABSOLUTLEY NECESSARY. PLEASE CLARIFY | | AND REVISE PLANS AS NECESSARY. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|