Plan Review Notes For Permit 02080638 |
Permit Number |
02080638 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-11-12 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) FROM PREVIOUS REVIEW: SHEET #3, | | SANITARY RISER DIAGRAM DOES NOT REFLECT | | THE FLOOR PLAN. THE DRINKING FOUNTAIN | | IS NOT SHOWN. DRINKING FOUNTAINS SHALL | | NOT DRAIN THROUGH THE THE WET VENT OF | | THE BATHROOM GROUPS 909.1/909.1.2. | | DRINKING FOUNTAINS SHALL DRAIN DOWN- | | STREAM OF THE BATHROOM GROUP. | | 2) NEW COMMENT: PLEASE PROVIDE A WATER | | RISER DIAGRAM. WATER HAMMER ARRESTORS | | PER 604.9 AND LOCATED NEAR THE FIXTURES | | WHERE REQUIRED NOT AT TOP OF DROP IN THE | | CEILING. BACKFLOW REQUIRED ON WATER | | SERVICE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|