2002-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: SHEET #3,
 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. THE DRINKING FOUNTAIN
 IS NOT SHOWN. DRINKING FOUNTAINS SHALL
 NOT DRAIN THROUGH THE THE WET VENT OF
 THE BATHROOM GROUPS 909.1/909.1.2.
 DRINKING FOUNTAINS SHALL DRAIN DOWN-
 STREAM OF THE BATHROOM GROUP.
 2) NEW COMMENT: PLEASE PROVIDE A WATER
 RISER DIAGRAM. WATER HAMMER ARRESTORS
 PER 604.9 AND LOCATED NEAR THE FIXTURES
 WHERE REQUIRED NOT AT TOP OF DROP IN THE
 CEILING. BACKFLOW REQUIRED ON WATER
 SERVICE.
  