Plan Review Notes For Permit 02080638 |
Permit Number |
02080638 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-28 00:00:00 | ************ NOTE ************* | | | | PLEASE NOTE , PLANS REDLINED AND NOTED | | THE NO MORETHAN 8' OF UNPROTECTED | | CONDUCTORS INSIDE BLDG PER 230-70A OF | | LOCAL AMENDMENTS. | | | | PLEASE NOTE ROOM FOR ELECTRICAL PANEL | | MUST MEET 110-26/ 384-7. SHOWN AS | | STORAGE AND EQUIPMENT ROOM.? | | | | NOTED ON PLANS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|