Plan Review Notes
Plan Review Notes For Permit 02080638
Permit Number 02080638
Review Stop B
Sequence Number 1
Notes
Date Text
2002-08-30 00:00:00THE LAND DESIGN SOUTH PLANS ARE REQUIRED
 TO BE SIGNED SEALED AND DATED.SEE
 FBC 104.2.2.
  
 SHOW THE ATTIC ACCESS REQUIRED BY FBC
 2309.6
  
 SHOW THE ATTIC VENTILATION REQUIRED BY
 FBC 2309.7 INCLUDE THE FREE AREA OF ANY
 SCREENED VENT TO BE USED.
  
 SHEET 3 OF 3 "DESIGN CHART" DECLARES
 ROOF ONLY, WHAT WAS USED FOR THE REST
 OF THE BUILDING?INCLUDE COMPONENTS
 AND CLADDING FOR THE WALLS.
  
 SEE FBC 104.2.1.1 FOR THE ROOF COVERING
 DESIGN INFORMATION TO BE PLACED ON THE
 PLANS.
  
 HOW WAS THE 0.18 +/- INTERNAL PRESSURE
 COEFFICIENT DETERMINED?SEE FBC
 1606.1.4.2 FOR ENCLOSED BUILDING
 CRITERIA.
  
 SHEET 3 OF3 CALLS OUT A "USP DTC"
 CONNECTOR FOR THE TRUSSES.USP DOES
 NOT LIST A "DTC" CONNECTOR IN THEIR
 CATALOG.WHAT IS INTENDED TO BE USED?
  
 WHAT GROUT SPECIFICATION AND VARIOUS
 OTHER SIGNIFICANT DESIGN CRITERIA ARE
 TO BE USED FOR THE FILLED CELL MASONRY?
 SEE FBC 2103.1.