2002-10-23 00:00:00 | APPROVED WITH PROVISO: |
| 1-REVISE TRUSS CONNECTOR TO MATCH USP |
| PUBLISHED LOADS. PROVIDE ENGINEERING |
| CALCS FOR DIFFERENT LOADS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| **NOTE: VALUES TO MATCH TYPE OF NAIL |
| USED. SEE USP CATALOGUE. |
| 2-PROVIDE ENGINEERING CALCULATIONS FOR |
| DETAIL 5/S3. SINCE FASTENERS ARE DIFFE |
| RENT THAN THOSE PUBLISHED BY USP. ALSO |
| CLARIFY HOW ARE TAPCONS FASTENED IF |
| THEY NEED TO BE 1 1/2" APART. SEE SIZE |
| OF CONNECTOR AND # OF FASTENERS. |
| **SPECIFY ON FLOOR PLAN THE CALCULATED |
| LOADS AT THIS CONNECTION. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 3-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS UNDER A SEPARATE |
| PERMIT. SEE CITY IMPLEMENTATION FOR |
| HURRICANE MISSILE IMPACT PROTECTION. |
| 4-PROVIDE SOIL TEST REPORT. |
| 5-ROOF SHEATHING & NAILING NOTE ON DWG |
| DWG S3 AND SECTION 4/S3 AND DIAPHRAGM |
| SCHEDULE HAVE DIFFERENT SPECS. REVISE/ |
| CLARIFY WHICH IS THE RIGHT FASTENER |
| AND SPACING TO BE USED. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 6-PROVIDE ENGINEERING CALCULATIONS FOR |
| 1" WASHER USED AT STRUCTURAL BUCK FOR |
| GARAGE. CONSIDER THE WOOD TYPE AND |
| REDUCTION FACTOR FOR P.T. WOOD. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |