2002-10-23 00:00:00APPROVED WITH PROVISO:
 1-REVISE TRUSS CONNECTOR TO MATCH USP
 PUBLISHED LOADS. PROVIDE ENGINEERING
 CALCS FOR DIFFERENT LOADS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 **NOTE: VALUES TO MATCH TYPE OF NAIL
 USED. SEE USP CATALOGUE.
 2-PROVIDE ENGINEERING CALCULATIONS FOR
 DETAIL 5/S3. SINCE FASTENERS ARE DIFFE
 RENT THAN THOSE PUBLISHED BY USP. ALSO
 CLARIFY HOW ARE TAPCONS FASTENED IF
 THEY NEED TO BE 1 1/2" APART. SEE SIZE
 OF CONNECTOR AND # OF FASTENERS.
 **SPECIFY ON FLOOR PLAN THE CALCULATED
 LOADS AT THIS CONNECTION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT. SEE CITY IMPLEMENTATION FOR
 HURRICANE MISSILE IMPACT PROTECTION.
 4-PROVIDE SOIL TEST REPORT.
 5-ROOF SHEATHING & NAILING NOTE ON DWG
 DWG S3 AND SECTION 4/S3 AND DIAPHRAGM
 SCHEDULE HAVE DIFFERENT SPECS. REVISE/
 CLARIFY WHICH IS THE RIGHT FASTENER
 AND SPACING TO BE USED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 6-PROVIDE ENGINEERING CALCULATIONS FOR
 1" WASHER USED AT STRUCTURAL BUCK FOR
 GARAGE. CONSIDER THE WOOD TYPE AND
 REDUCTION FACTOR FOR P.T. WOOD. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.