2002-09-06 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-A)SPECIFY FIREBLOCKING MATERIAL AND |
| LOCATION AT STAIRS. INCLUDING TOP OF |
| STAIRS. SEE SEC. 2305.1.4 FBC 2001. |
| B)PROVIDE GENERAL SPECS FOR REQUIRED |
| FIREBLOCKING AT ALL CONCEALED SPACES. |
| SEE SEC. 2305.1.4 FBC 2001. |
| 3-2ND. FLOOR FRAMING PLAN: DRAFSTOPPING |
| TO BE LOCATED AT AREAS NOT TO EXCEED |
| 500 S.F. REVISE AS REQUIRED. SEE SEC. |
| 2305.2.2 FBC 2001. |
| 4-SPECIFY FIRECUT REQUIREMENTS ON THE |
| STRUCTURAL WALL SECTIONS. SEE SECTION |
| 2305.4 FBC 2001. |
| 5-SPECIFY SUPPORTS AND SPACING FOR WWM |
| IN CONCRETE SLAB. SEE SEC. 1909.3 FBC. |
| 6-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS OR APPLY FOR A |
| SEPARATE PERMIT. CITY IMPLEMENTATION |
| STANDARD FOR HURRICANE MISSILE IMPACT |
| PROTECTION. |
| 7-REVISE STAIR KEY NOTE #1. HEIGHT OF |
| STAIR HANDRAIL TO BE BET. 34" AND 38". |
| SEE SEC. 1007.5.1 FBC 2001. |
| 8-SECOND FLOOR FRAMING PLAN: |
| PROVIDE DETAIL SHOWING HOW DOES USP |
| HL210 WHICH IS A LIGHT GAUGE PURLING |
| HANGER IS USED TO HOLD GIRDER TRUSS. |
| **SEE USP CATALOGUE FOR PROPER LOADS |
| FOR THIS TYPE OF CONNECTOR. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 9-SECTION 4/S3 IS CALLED 5/S3 ON ROOF |
| FRAMING PLAN. CLARIFY/REVISE AS REQ'D. |
| 10-REVISE DETAIL 4/S3 TO SHOW GABLE END. |
| ***NOTE: GABLE END TO BE DESIGNED AS PER |
| SEC. 2117 FBC 2001. PROVIDE COMPLETE |
| DETAIL AND SPECS AND SPECIFY ALL |
| FASTENERS. |
| 11-REVISE TRUSS CONNECTOR SCHEDULE TO |
| MATCH USP PUBLISHED LOADS. |
| **NOTE: PROVIDE ENGINEERING CALCS FOR |
| LOADS OTHER THAN THOSE PUBLISHED. |
| **REMAINDER: 10D NAILS NEED 1 3/4" MIN. |
| PENETRATION TO GET THE FULL VALUE. DO |
| NOT MISMATCH NAIL SIZE AND LOADS. |
| 12-THERE IS NOT CONNECTOR SPECIFIED FOR |
| ROOF TRUSS WITH CALCULATED UPLIFT LOAD |
| OF 2537#. |
| 13-CONNECTOR T-5 DOESN'T RESIST THE |
| UPLIFT LOAD OF 2369# CALCULATED FOR |
| ROOF GIRDER TRUSS. SEE ROOF FRAMING |
| PLAN. |
| 14-ROOF SHEATHING & NAILING NOTE ON |
| DWG S3 AND SECTION 4/S3 AND DIAPHRAGM |
| SCHEDULE HAVE DIFFERENT SPECS. REVISE/ |
| CLARIFY AS REQUIRED. |
| **NOTE: KEEP IN MIND THAT MEAN ROOF HT. |
| BET. 25" AND 35" REQUIRES 8D RING |
| SHANK NAILS MIN. SEE TABLE 2306.1 CITY |
| AMENDMENTS TO FBC 2001. |
| 15-IDENTIFY NAILING ZONES IN ROOF FRAM'G |
| PLAN. SEE TABLE 2306.1 CITY AMENDMENTS |
| 16-DESIGN PRESSURES FOR ENTRY DOORS ARE |
| DIFFERENT ON THE FLOOR PLAN AND THE |
| EXTERIOR ELEVATION. REVISE/CLARIFY. |
| 17-SEE GARAGE DOOR PRODUCT APPROVAL FOR |
| STRUCTURAL BUCK REQUIREMENTS & REVISE |
| DETAIL AS REQUIRED. |
| **NOTE: SPECIFY SIZE FOR WASHERS. |
| 18-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| INSTALLATION OF DOUBLE 2X BUCK TO |
| ACCOMMODATE THE ENTRY DOORS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 19-UPDATE DRAWING C-1: FOUNDATION NOTE |
| STILL CALLS FOR 0.004 MIL VISQEEN. |
| NEED 0.006 MIL MIN. SEC. 1909.2 FBC. |
| 20-UPDATE NOTE #3 SHEET S3. REFERENCE |
| FBC 2001 OR ASCE 7-98, NOT ASCE 7-93. |
| 21-SHEET A-4: EXTERIOR ELEVATIONS ARE NO |
| SHOWN AT 1/4" SCALE. REVISE AS REQ'D. |
| 22-UPDATE PLUMBING NOTE #6 ON SHEET A-2. |
| 23-REVIEW NOMENCLATURE USED FOR SECTIONS |
| AND DETAILS.LETTER AND SHEET NUMBERS |
| DON'T MATCH. EG: SEE SECTION A/6. ALL |
| DETAILS ON THIS SHEET SHALL BE A7 NOT |
| A6. SEE FLOOR PLANS AND SHEET A7. |
| 24-SPECIFY FIREBLOCKING ON SECTION A/A7. |
| SEE SEC. 2305.1.4 FBC 2001. |