2002-09-06 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-A)SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AT STAIRS. INCLUDING TOP OF
 STAIRS. SEE SEC. 2305.1.4 FBC 2001.
 B)PROVIDE GENERAL SPECS FOR REQUIRED
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEE SEC. 2305.1.4 FBC 2001.
 3-2ND. FLOOR FRAMING PLAN: DRAFSTOPPING
 TO BE LOCATED AT AREAS NOT TO EXCEED
 500 S.F. REVISE AS REQUIRED. SEE SEC.
 2305.2.2 FBC 2001.
 4-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEE SECTION
 2305.4 FBC 2001.
 5-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC.
 6-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR A
 SEPARATE PERMIT. CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION.
 7-REVISE STAIR KEY NOTE #1. HEIGHT OF
 STAIR HANDRAIL TO BE BET. 34" AND 38".
 SEE SEC. 1007.5.1 FBC 2001.
 8-SECOND FLOOR FRAMING PLAN:
 PROVIDE DETAIL SHOWING HOW DOES USP
 HL210 WHICH IS A LIGHT GAUGE PURLING
 HANGER IS USED TO HOLD GIRDER TRUSS.
 **SEE USP CATALOGUE FOR PROPER LOADS
 FOR THIS TYPE OF CONNECTOR.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 9-SECTION 4/S3 IS CALLED 5/S3 ON ROOF
 FRAMING PLAN. CLARIFY/REVISE AS REQ'D.
 10-REVISE DETAIL 4/S3 TO SHOW GABLE END.
 ***NOTE: GABLE END TO BE DESIGNED AS PER
 SEC. 2117 FBC 2001. PROVIDE COMPLETE
 DETAIL AND SPECS AND SPECIFY ALL
 FASTENERS.
 11-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP PUBLISHED LOADS.
 **NOTE: PROVIDE ENGINEERING CALCS FOR
 LOADS OTHER THAN THOSE PUBLISHED.
 **REMAINDER: 10D NAILS NEED 1 3/4" MIN.
 PENETRATION TO GET THE FULL VALUE. DO
 NOT MISMATCH NAIL SIZE AND LOADS.
 12-THERE IS NOT CONNECTOR SPECIFIED FOR
 ROOF TRUSS WITH CALCULATED UPLIFT LOAD
 OF 2537#.
 13-CONNECTOR T-5 DOESN'T RESIST THE
 UPLIFT LOAD OF 2369# CALCULATED FOR
 ROOF GIRDER TRUSS. SEE ROOF FRAMING
 PLAN.
 14-ROOF SHEATHING & NAILING NOTE ON
 DWG S3 AND SECTION 4/S3 AND DIAPHRAGM
 SCHEDULE HAVE DIFFERENT SPECS. REVISE/
 CLARIFY AS REQUIRED.
 **NOTE: KEEP IN MIND THAT MEAN ROOF HT.
 BET. 25" AND 35" REQUIRES 8D RING
 SHANK NAILS MIN. SEE TABLE 2306.1 CITY
 AMENDMENTS TO FBC 2001.
 15-IDENTIFY NAILING ZONES IN ROOF FRAM'G
 PLAN. SEE TABLE 2306.1 CITY AMENDMENTS
 16-DESIGN PRESSURES FOR ENTRY DOORS ARE
 DIFFERENT ON THE FLOOR PLAN AND THE
 EXTERIOR ELEVATION. REVISE/CLARIFY.
 17-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK REQUIREMENTS & REVISE
 DETAIL AS REQUIRED.
 **NOTE: SPECIFY SIZE FOR WASHERS.
 18-PROVIDE STRUCTURAL BUCK DETAIL FOR
 INSTALLATION OF DOUBLE 2X BUCK TO
 ACCOMMODATE THE ENTRY DOORS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 19-UPDATE DRAWING C-1: FOUNDATION NOTE
 STILL CALLS FOR 0.004 MIL VISQEEN.
 NEED 0.006 MIL MIN. SEC. 1909.2 FBC.
 20-UPDATE NOTE #3 SHEET S3. REFERENCE
 FBC 2001 OR ASCE 7-98, NOT ASCE 7-93.
 21-SHEET A-4: EXTERIOR ELEVATIONS ARE NO
 SHOWN AT 1/4" SCALE. REVISE AS REQ'D.
 22-UPDATE PLUMBING NOTE #6 ON SHEET A-2.
 23-REVIEW NOMENCLATURE USED FOR SECTIONS
 AND DETAILS.LETTER AND SHEET NUMBERS
 DON'T MATCH. EG: SEE SECTION A/6. ALL
 DETAILS ON THIS SHEET SHALL BE A7 NOT
 A6. SEE FLOOR PLANS AND SHEET A7.
 24-SPECIFY FIREBLOCKING ON SECTION A/A7.
 SEE SEC. 2305.1.4 FBC 2001.