Plan Review Notes For Permit 02080610
Permit Number 02080610
Review Stop R
Sequence Number 2
Notes
Date Text
2002-11-05 00:00:00APPROVED WITH PROVISO:
 1-CLARIFY INFO. FOR STORM SHUTTERS:
 A)DESIGN PRESSURES SPECIFIED LIMIT THE
 STORM PANEL SPAN. SEE ARCHITECTURAL
 DWGS FOR CALCULATED DESIGN PRESSURES &
 REVISE AS REQUIRED.
 B)CLARIFY WHICH ANCHOR TO BE USED RAWL
 OR CAULK-IN.
 C)MARK ON DRAWINGS MOUNTING CONDITIONS &
 ANCHOR TYPE AND SPACING.
  
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY AS SHOWN
 ON PLANS.
 3-PROVIDE CLEAR/LEGIBLE PRODUCT APPROVAL
 FOR GLASS BLOCK.
 4-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA. SEE SECTION
 602.1.ABC.1.2 CHAPTER 13 FBC 2001.
 B)OWNER/AGENT TO SIGN AND DATE FORM TOO.
  
 5-REVISE TRUSS ANCHOR SCHEDULE TO MATCH
 USP CATALOGUE ACCORDING TO NAIL USED.
 PROVIDE ENGINEERING CALCULATIONS FOR
 DIFFERENT VALUES. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 6-FOUNDATION PLAN AND FOOTING SCHEDULE
 DON'T MATCH. REVISE AS REQUIRED. ALSO,
 WALL SECTIONS DIMENSIONS (L X W) DON'T
 MATCH LENGTH AND WIDTH AS SHOWN ON THE
 FOOTING SCHEDULE. REVISE AS REQUIRED.