Plan Review Notes For Permit 02080610 |
Permit Number |
02080610 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-11-05 00:00:00 | APPROVED WITH PROVISO: | | 1-CLARIFY INFO. FOR STORM SHUTTERS: | | A)DESIGN PRESSURES SPECIFIED LIMIT THE | | STORM PANEL SPAN. SEE ARCHITECTURAL | | DWGS FOR CALCULATED DESIGN PRESSURES & | | REVISE AS REQUIRED. | | B)CLARIFY WHICH ANCHOR TO BE USED RAWL | | OR CAULK-IN. | | C)MARK ON DRAWINGS MOUNTING CONDITIONS & | | ANCHOR TYPE AND SPACING. | | | | 2-PROVIDE PRODUCT APPROVAL FOR ENTRY | | DOOR WITH SIDELITE ASSEMBLY AS SHOWN | | ON PLANS. | | 3-PROVIDE CLEAR/LEGIBLE PRODUCT APPROVAL | | FOR GLASS BLOCK. | | 4-ENERGY CALCULATIONS: | | A)REVISE UNDER ATTIC AREA. SEE SECTION | | 602.1.ABC.1.2 CHAPTER 13 FBC 2001. | | B)OWNER/AGENT TO SIGN AND DATE FORM TOO. | | | | 5-REVISE TRUSS ANCHOR SCHEDULE TO MATCH | | USP CATALOGUE ACCORDING TO NAIL USED. | | PROVIDE ENGINEERING CALCULATIONS FOR | | DIFFERENT VALUES. SECTION 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | 6-FOUNDATION PLAN AND FOOTING SCHEDULE | | DON'T MATCH. REVISE AS REQUIRED. ALSO, | | WALL SECTIONS DIMENSIONS (L X W) DON'T | | MATCH LENGTH AND WIDTH AS SHOWN ON THE | | FOOTING SCHEDULE. REVISE AS REQUIRED. |
|