2002-09-13 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE ENGINEERING ANALYSIS/CALCS
 SHOWING HOW THE MAIN WIND FORCE RESIS-
 TING SYSTEM (MWFRS) WAS DESIGNED TO
 TRANSFER LOADS THRU FLOOR AND CEILING
 DIAPHRAGMS CONSIDERING THE DOUBLE
 CEILING AREA AND THE PARTIAL FL. DIA-
 PHRAGM SUPPORTED ON WOOD COLUMNS WITH
 CONNECTORS (TOP AND BOTTOM) THAT DON'T
 PROVIDE SUPPORT FOR LATERAL FORCES.
 SEE SEC. 1606.2.4 FBC 2001.
 3-PROVIDE ENGINEERING ANALYSIS/CALCS
 SHOWING MASONRY WALLS LATERAL STABILI-
 TY (SEE SEC. 2105 FBC 2001) AND LATE-
 RAL SUPPORT (SEE SEC. 2107 FBC 2001)
 CONSIDERING THE HIGH VOLUME AREA AND
 SINGLE BOND BEAM ONLY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-A)PROVIDE FIREBLOCKING AT STAIRS. IN-
 CLUDING TOP AREA. SEC. 2305.1.4 FBC.
 B)SPECIFY FIREBLOCKING AT ALL WALL SEC-
 TIONS AND PROVIDE GENERAL SPECS FOR
 REQUIRED FIREBLOCKING AT ALL CONCEALED
 SPACES. SEC. 2305.1.4 FBC 2001.
 5-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR SEPARA
 TE PERMIT. SEE CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION.
 **NOTE: SEE LIMITATIONS ON PRODUCT
 APPROVAL SUBMITTED.
 6-PROVIDE DETAIL/SPECS FOR ONE HR FIRE
 RATED WALL ASSEMBLY @ FRAMED WALL AREA
 ABOVE BOND BEAM AT ZERO LOT LINE WALL
 AS REQ'DBY TABLE 600 FBC 2001.
 7-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOWS AT FRAMED AREA.
 **NOTE; NEED SPECS FOR ATTACHMENT TO
 MASONRY WALL AS WELL. SEE EXT. ELEV.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-NOTE #2 ON A-1 CALL FOR WINDOW TO BE
 RECESSED TO ALLOW FOR STORM SHUTTERS
 INSTALLATION. PROVIDE COMPLETE STRUCT-
 URAL DETAIL/SPECS. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 **NOTE: SEE PRODUCT APPROVAL FOR TRACK
 AND MOUNTING CONDITIONS CONSIDERING
 THE GLASS DISTANCE & THE EDGE DISTANCE
 9-SEE PRODUCT APPROVAL FOR GARAGE DOOR
 STRUCTURAL BUCK REQUIREMENTS & PROVIDE
 DETAIL AS REQUIRED. SPECIFY ANCHOR
 SIZE AND REQUIRED WASHER. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 11-STAIR FLOOR PALN: CLARIFY NOTE #13.
 THERE IS NOT POST WHERE ARROW IS POIN-
 TING. SEE PLAN ON SHEET A-5.
 12-IF WOOD COLUMNS ARE CHANGED TO STEEL,
 THEN UPDATE STAIR FRAMIN DETAILS.
 13-SPECIFY SPACING FOR WWM IN CONCRETE
 SLAB. SEE SEC. 1909.3 FBC 2001.
 14-SHEET S-1:A)SOME INFORMATION IS OVER-
 LAPPING. B)COLUMN F6 DOESN'T MATCH
 SCHEDULE.
 15-IDENTIFY ROOF ZONES IN ROOF FRAMING
 PLAN. TABLE 2306.1 CITY AMENDMENTS.
 16-REVISE TRUSS CONNECTOR TO MATCH USP
 PUBLISHED VALUES. PROVIDE ENGINEERING
 CALCS FOR DIFFERENT VALUES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 17-PROVIDE ATTIC ACCESS ABOVE GARAGE AND
 MORNING ROOM IF CLEAR HEIGHT IS MORE
 THAN 24". SEE SEC. 2309.6 FBC 2001.
 18-24SH AND 34SH WINDOWS DON'T PROVIDE
 MIN. CLEAR HEIGHT REQ'D FOR EGRESS.
 SEE SEC. 1005.4.4 FBC 2001.
 **NOTE: MAKE SURE THAT WINDOWS ON 2ND.
 FL. WIL HAVE 5.7 S.F. MIN. CLEAR OP'G.
 19-UPDATE SHEET C-1. FOUNDATION NOTE
 STILL CALLS FOR 0.004 MIL VISQUEEN.
 NEED 0.006 MIL MIN. SEC. 1909.2 FBC.
 20-SHEET A-1: WHERE IS SEC/5 SHOWN ON
 FLOOR PLAN BY GARAGE ENTRY.
 21-REVISE SIZE OF ATTIC ACCESS. 36" MIN.
 SEC. 2309.6 FBC 2001.
 22-SHEET A-2: UPDATE GENERAL NOTE FOR
 PLUMBING. REFERENCE FPC 2001.
 23-SHEET A-3: A)SOME INFORMATION IS OVER
 LAPPING. SEE FRONT ELEVATION. B)REVISE
 NOTE #4 FOR FRAMING AT ARCHED OPENINGS
 AND FOR ONE HOUR FIRE RATED WALL AT
 ZERO LOT LINE WALL.
 24-SHEET A-5: A)STAIRS CALCULATIONS ARE
 NOT CLEAR. B)UPDATE SEMCO STRAP. C)
 HANDRAIL DIMENSION IS NOT CLEAR. OVER-
 LAPPING INFORMATION. D)KEY NOTE #14:
 DRAFTSTOPPING IS NOT THE SAME AS FIRE-
 BLOCKING. SEE SEC. 2305.1.4 FBC 2001.
 ALSO, FIREBLOCKING SHOWN AT THE MIDDLE
 OF STAIRS IS INCORRECT. IT DOESN'T
 PROVIDE ANY FIREBLOCKING THE WAY IT'S
 SHOWN.
 25-SHEET S-1:A)WHERE IS SEC/5?. B)IF
 USING WOOD COLUMN, THEN REMEMBER TO
 UPDATE SEMCO CONNECTORS. C)WHERE IS
 COLUMN P3 SPECIFIED ON 2ND FL FRAMING?
 26-SHEET S-2: A)REVISE SEMCO CONNECTORS
 SPECIFIED ON SECTION 5. B)SPECIFY
 DRAFTSTOPPING LOCATION AND MATERIAL.
 SEE SEC. 2305.2.2 FBC 2001. C)PROVIDE
 SECTION/DETAIL SHOWING HOW IS BEAM
 2B-1 ANCHORED TO THE MASONRY COLUMNS
 AT THE ENDS. SEC. 104.2.1.2 CITY AMEND
 MENTS TO FBC 2001.*SAME PPLIES TO BEAM
 AT MORNING ROOM AREA. D)CLARIFY SECT'N
 #2: BB WITH 1 #7 OR BB WITH 1#5?.
 E)FLOOR PLAN SHALL BE CALLED SECOND
 FLOOR FRAMING PLAN, NOT GROUND FLOOR.
 PLAN.