Plan Review Notes
Plan Review Notes For Permit 02080496
Permit Number 02080496
Review Stop R
Sequence Number 2
Notes
Date Text
2002-11-08 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-FLOOD ZONE A8. WILL NEED TO PROVIDE
 THE ELEVATI0N CERTIFICATE.
 2-PROVIDE UL SPECS FOR 1 HR FIRE RATED
 GLASS BLOCK ASSEMBLY AS REQUIRED BY
 TABLE 600 FBC 2001.
 **ALSO, PROVIDE LEGIBLE PRODUCT APPROVAL
 AND DRAWINGS FOR GLASS BLOCK.
 3-PROVIDE SOIL TEST REPORT.
 4-STORM SHUTTERS: A)DESIGN PRESSURES
 SPECIFIED ON INSTALLATION SCHEDULE
 HAVE LIMITATIONS ON PANELS SPAN. SEE
 CALCULATED DESIGN PRESSURES BY ARCH.
 AND REVISE AS REQUIRED. ALSO, CLARIFY
 WHICH ANCHOR USED RAWL OR CAULK-IN.
 B)MARK ON DRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE & SPACING
 TO BE USED.
 5-SECOND FLOOR FRAMING PLAN: SPECIFY
 DRAFSTOPPING LOCATION AT AREAS NOT TO
 EXCEED 500 SF. SEE SEC. 2305.2.2 FBC.
 6-SPECIFY SIZE OF ANCHOR BOLT AND WASHER
 FOR GARAGE STRUCTURAL BUCK DETAIL.