Plan Review Notes For Permit 02080496 |
Permit Number |
02080496 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-11-08 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-FLOOD ZONE A8. WILL NEED TO PROVIDE | | THE ELEVATI0N CERTIFICATE. | | 2-PROVIDE UL SPECS FOR 1 HR FIRE RATED | | GLASS BLOCK ASSEMBLY AS REQUIRED BY | | TABLE 600 FBC 2001. | | **ALSO, PROVIDE LEGIBLE PRODUCT APPROVAL | | AND DRAWINGS FOR GLASS BLOCK. | | 3-PROVIDE SOIL TEST REPORT. | | 4-STORM SHUTTERS: A)DESIGN PRESSURES | | SPECIFIED ON INSTALLATION SCHEDULE | | HAVE LIMITATIONS ON PANELS SPAN. SEE | | CALCULATED DESIGN PRESSURES BY ARCH. | | AND REVISE AS REQUIRED. ALSO, CLARIFY | | WHICH ANCHOR USED RAWL OR CAULK-IN. | | B)MARK ON DRAWINGS SPECIFIC MOUNTING | | CONDITIONS AND ANCHOR TYPE & SPACING | | TO BE USED. | | 5-SECOND FLOOR FRAMING PLAN: SPECIFY | | DRAFSTOPPING LOCATION AT AREAS NOT TO | | EXCEED 500 SF. SEE SEC. 2305.2.2 FBC. | | 6-SPECIFY SIZE OF ANCHOR BOLT AND WASHER | | FOR GARAGE STRUCTURAL BUCK DETAIL. |
|