Plan Review Notes
Plan Review Notes For Permit 02080496
Permit Number 02080496
Review Stop R
Sequence Number 1
Notes
Date Text
2002-08-27 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-SHEET C-1: UPDATE NOTE #1. NEED 0.006
 MIL MIN. VAPOR BARRIER. SEC. 1909.2
 3-GABLE END CONTRUCTION AT ZERO LOT LINE
 TO BE 1 HR FIRE RATED ASSEMBLY REQ'D
 BY TABLE 600 FBC 2001. REVISE AS REQ'D
 4-24SH & 34SH WINDOWS DON'T PROVIDE THE
 24" MIN. CLEAR OPENING. SEC. 1005.4.4
 FBC 2001. ALSO, CHECK FOR 5.7 S.F. MIN
 CLEAR OPENING @ 2ND. FLOOR.
 5-PROVIDE FIREBLOCKING AT STAIRS. SEE
 SEC. 2305.1.4 FBC 2001.
 **NOTE: PROVIDE GENERAL SPECIFICATIONS
 FOR FIREBLOCKING AT ALL CONCEALED
 SPACES. SEC. 2305.1.4 FBC 2001.
 5-SECTION A/A4 AND SECTION/DETAIL R19:
 PROVIDE COMPLETE DETAIL/SPECS TO
 SATISFY REQUIREMENTS OF SEC. 2117 FBC
 2001 FOR GABLE END CONTINUITY.
 6-SPECIFY FIRECUT REQUIREMENTS ON
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 7-PROVIDE DETAIL SHOWING ATTACHMENT OF
 DOUBLE 2X STRUCTURAL BUCK @ ENTRY DOOR
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 8-EXTERIOR ELEVATIONS AND ROOF FRAMING
 PLAN DON'T MATCH. REVISE AS REQUIRED.
 9-DETAIL F14: SPECIFY HOW LONG ARE THE
 BOLTS SPECIFIED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 10-DETAIL S21 DOESN'T WORK FOR WOOD COL.
 P1 LOCATED BET. GARAGE & STAIRWAY TO
 RECEIVE 2GIRDER TRUSSES. REVISE AS
 REQUIRED.
 **NOTE: VERIFY THAT TOP & BOTT. WOOD COL
 CONNECTORS WILL RESIST ALL LOADS THAT
 ARE TRANSFERRED FROM FLOOR DIAPHRAGM.
 11-UPDATE TRUSS CONNECTOR TO MATCH USP
 CATALOGUE. PROVIDE ENGINEERING CALCS
 FOR VALUES DIFFERENT THAN THOSE IN
 USP CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 12-CONNECTOR TC-1 SPECIFIED ON ROOF
 FRAMING PLAN FOR FRAMED WALL ARE WOOD
 TO CONCRETE CONNECTORS. NEED WOOD TO
 WOOD CONNECTORS. REVISE AS REQUIRED.
 13-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR 1 HR. FIRE RATED GLASS BLOCK
 ASSEMBLY AS REQ'D BY TABLE 600 FBC.
 REVISE GLASS BLOCK DETAIL AS REQUIRED.
 14-FLOOD ZONE A8. WILL NEED ELEVATION
 CERTIFICATE AS REQUIRED BY FEMA.
 15-PROVIDE SOIL TEST REPORT.
 16-STORM SHUTTERS:
 A)ROBICO SHUTTERS ENGINEER IS LIMITING
 THIS PRODUCT APPROVAL TO BE SIGNED AND
 SEALED BY HIM TO BE USED FOR PERMIT.
 SEE GENERAL NOTE #6 ON SHEET 1 OF 9.
 THEREFORE, NEED SIGNED AND SEALED
 DRAWINGS TO USE THIS PRODUCT.
 B)PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE THAT MATCH PLANS SUBMITTED.
 CHECK ALL OPENINGS.
 C)SOME SHUTTERS WILL BE INSTALLED ON
 FRAMED WALLS. INSTALLATION SCHEDULE
 SHOWS SAME CONNECTOR FOR CONCRETE WOOD
 & CONCRETE BLOCK APPLICATIONS. REVISE.
 D)CLEARLY MARK ON SHUTTERDRAWINGS AND
 ANCHOR SCHEDULE (SHEET 7 OF 9) THE
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE & SPACING TO BE USED ACCORDING TO
 THE MEAN ROOF HT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK OR WOOD).
 17-SPECIFY DRAFSTOPPING MATERAIL AND
 LOCATION ON SECOND FLOOR FRAMING PLAN.
 SEC. 2305.2.2 FBC 2001.
 **NOTE: AREAS SEPARATED TO BE NO MORE
 THAN 500 S.F. SEC. 2305.2.2 FBC 2001.
 18-SEE PRODUCT APPROVAL FOR GARAGE DOOR
 STRUCTURAL BUCK SPCIFICATIONS AND
 REVISE DETAIL AS REQUIRED.
 19-SPECIFY SPACING FOR WWM SUPPORTS IN
 CONCRETE SLAB. SEE SEC 1909.3 FBC 2001
 20-ROOF FRAMING PLAN: IDENTIFY ROOF NAIL
 ING ZONES.
 21-SHEET A-2: UPDATE GENERAL NOT #6.
 USE FBC 2001, NOT SBC 1994.
 22-SPECIFY CONNECTOR @ OUTLOOKER DETAIL
 ON DRAWING A-3.
 23-SHEET S-1: CLARIFY WHICH DETAIL IS
 THE ONE THAT APPLIES TO WOOD SHEARWALL
 R4 OR S19 BECAUSE THESE ARE TWO DIFFE-
 RENT APPLICATIONS.
 24-SHEET S-4:
 A)REVISE DETAILS R6, R7, R13 AND R4.
 **SPECIFY HOW LONG ARE THE LAG BOLTS.
 **CLARIFY SPACING OF LAG BOLTS. (16"
 OR 24").
 **CLARIFY CONNECTOR USED:RT12T OR RT16
 **CLARIFY HOW IS CONNECTOR USP RT16
 INSTALLED TO CONNECT TOP AND BOTTOM
 PLATES TO THE 3 STUDS AT THE END OF
 SHEARWALL. SEE DETAIL R4 AND PAGE 50
 OF USP BOOK FOR TYPE OF CONNECTOR.
 B)DETAIL R7: CLARIFY HOW IS SHEARWALL
 ANCHORED AT SIDES OF OPENINGS. THIS
 DETAIL DOESN'T SHOW ANY HOLDDOWNS AT
 BOTTOM OF FULL HEIGHT STUDS.