2002-08-27 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-SHEET C-1: UPDATE NOTE #1. NEED 0.006 |
| MIL MIN. VAPOR BARRIER. SEC. 1909.2 |
| 3-GABLE END CONTRUCTION AT ZERO LOT LINE |
| TO BE 1 HR FIRE RATED ASSEMBLY REQ'D |
| BY TABLE 600 FBC 2001. REVISE AS REQ'D |
| 4-24SH & 34SH WINDOWS DON'T PROVIDE THE |
| 24" MIN. CLEAR OPENING. SEC. 1005.4.4 |
| FBC 2001. ALSO, CHECK FOR 5.7 S.F. MIN |
| CLEAR OPENING @ 2ND. FLOOR. |
| 5-PROVIDE FIREBLOCKING AT STAIRS. SEE |
| SEC. 2305.1.4 FBC 2001. |
| **NOTE: PROVIDE GENERAL SPECIFICATIONS |
| FOR FIREBLOCKING AT ALL CONCEALED |
| SPACES. SEC. 2305.1.4 FBC 2001. |
| 5-SECTION A/A4 AND SECTION/DETAIL R19: |
| PROVIDE COMPLETE DETAIL/SPECS TO |
| SATISFY REQUIREMENTS OF SEC. 2117 FBC |
| 2001 FOR GABLE END CONTINUITY. |
| 6-SPECIFY FIRECUT REQUIREMENTS ON |
| STRUCTURAL WALL SECTIONS. SEC. 2305.4 |
| 7-PROVIDE DETAIL SHOWING ATTACHMENT OF |
| DOUBLE 2X STRUCTURAL BUCK @ ENTRY DOOR |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| 8-EXTERIOR ELEVATIONS AND ROOF FRAMING |
| PLAN DON'T MATCH. REVISE AS REQUIRED. |
| 9-DETAIL F14: SPECIFY HOW LONG ARE THE |
| BOLTS SPECIFIED. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 10-DETAIL S21 DOESN'T WORK FOR WOOD COL. |
| P1 LOCATED BET. GARAGE & STAIRWAY TO |
| RECEIVE 2GIRDER TRUSSES. REVISE AS |
| REQUIRED. |
| **NOTE: VERIFY THAT TOP & BOTT. WOOD COL |
| CONNECTORS WILL RESIST ALL LOADS THAT |
| ARE TRANSFERRED FROM FLOOR DIAPHRAGM. |
| 11-UPDATE TRUSS CONNECTOR TO MATCH USP |
| CATALOGUE. PROVIDE ENGINEERING CALCS |
| FOR VALUES DIFFERENT THAN THOSE IN |
| USP CATALOGUE. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 12-CONNECTOR TC-1 SPECIFIED ON ROOF |
| FRAMING PLAN FOR FRAMED WALL ARE WOOD |
| TO CONCRETE CONNECTORS. NEED WOOD TO |
| WOOD CONNECTORS. REVISE AS REQUIRED. |
| 13-PROVIDE UL LISTING AND COMPLETE SPECS |
| FOR 1 HR. FIRE RATED GLASS BLOCK |
| ASSEMBLY AS REQ'D BY TABLE 600 FBC. |
| REVISE GLASS BLOCK DETAIL AS REQUIRED. |
| 14-FLOOD ZONE A8. WILL NEED ELEVATION |
| CERTIFICATE AS REQUIRED BY FEMA. |
| 15-PROVIDE SOIL TEST REPORT. |
| 16-STORM SHUTTERS: |
| A)ROBICO SHUTTERS ENGINEER IS LIMITING |
| THIS PRODUCT APPROVAL TO BE SIGNED AND |
| SEALED BY HIM TO BE USED FOR PERMIT. |
| SEE GENERAL NOTE #6 ON SHEET 1 OF 9. |
| THEREFORE, NEED SIGNED AND SEALED |
| DRAWINGS TO USE THIS PRODUCT. |
| B)PROVIDE KEY PLAN AND INSTALLATION |
| SCHEDULE THAT MATCH PLANS SUBMITTED. |
| CHECK ALL OPENINGS. |
| C)SOME SHUTTERS WILL BE INSTALLED ON |
| FRAMED WALLS. INSTALLATION SCHEDULE |
| SHOWS SAME CONNECTOR FOR CONCRETE WOOD |
| & CONCRETE BLOCK APPLICATIONS. REVISE. |
| D)CLEARLY MARK ON SHUTTERDRAWINGS AND |
| ANCHOR SCHEDULE (SHEET 7 OF 9) THE |
| SPECIFIC MOUNTING CONDITIONS & ANCHOR |
| TYPE & SPACING TO BE USED ACCORDING TO |
| THE MEAN ROOF HT, DESIGN PRESSURES, |
| EDGE DISTANCE, PANEL SPAN, CONNECTION |
| TYPE AND STRUCTURE TO BE ATTACHED TO |
| (CONCRETE BLOCK OR WOOD). |
| 17-SPECIFY DRAFSTOPPING MATERAIL AND |
| LOCATION ON SECOND FLOOR FRAMING PLAN. |
| SEC. 2305.2.2 FBC 2001. |
| **NOTE: AREAS SEPARATED TO BE NO MORE |
| THAN 500 S.F. SEC. 2305.2.2 FBC 2001. |
| 18-SEE PRODUCT APPROVAL FOR GARAGE DOOR |
| STRUCTURAL BUCK SPCIFICATIONS AND |
| REVISE DETAIL AS REQUIRED. |
| 19-SPECIFY SPACING FOR WWM SUPPORTS IN |
| CONCRETE SLAB. SEE SEC 1909.3 FBC 2001 |
| 20-ROOF FRAMING PLAN: IDENTIFY ROOF NAIL |
| ING ZONES. |
| 21-SHEET A-2: UPDATE GENERAL NOT #6. |
| USE FBC 2001, NOT SBC 1994. |
| 22-SPECIFY CONNECTOR @ OUTLOOKER DETAIL |
| ON DRAWING A-3. |
| 23-SHEET S-1: CLARIFY WHICH DETAIL IS |
| THE ONE THAT APPLIES TO WOOD SHEARWALL |
| R4 OR S19 BECAUSE THESE ARE TWO DIFFE- |
| RENT APPLICATIONS. |
| 24-SHEET S-4: |
| A)REVISE DETAILS R6, R7, R13 AND R4. |
| **SPECIFY HOW LONG ARE THE LAG BOLTS. |
| **CLARIFY SPACING OF LAG BOLTS. (16" |
| OR 24"). |
| **CLARIFY CONNECTOR USED:RT12T OR RT16 |
| **CLARIFY HOW IS CONNECTOR USP RT16 |
| INSTALLED TO CONNECT TOP AND BOTTOM |
| PLATES TO THE 3 STUDS AT THE END OF |
| SHEARWALL. SEE DETAIL R4 AND PAGE 50 |
| OF USP BOOK FOR TYPE OF CONNECTOR. |
| B)DETAIL R7: CLARIFY HOW IS SHEARWALL |
| ANCHORED AT SIDES OF OPENINGS. THIS |
| DETAIL DOESN'T SHOW ANY HOLDDOWNS AT |
| BOTTOM OF FULL HEIGHT STUDS. |