Plan Review Notes For Permit 02080494 |
Permit Number |
02080494 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-11-01 00:00:00 | APPROVED WITH PROVISO: | | 1-STORM SHUTTERS: A)DESIGN PRESSURES | | SPECIFIED HAVE LIMITATIONS ON THE | | STORM PANEL MAX. SPAN. SEE PLANS FOR | | CALCULATED DESIGN PRESSURES AND REVISE | | AS REQUIRED. | | B)CLARIFY WHICH TYPE OF ANCHOR IS USED | | RAWL OR CAULK-IN? | | C)CIRCLE/IDENTIFY ON STORM PANEL DWGS | | INSTALLATION SCHEDULE ANCHOR TYPE AND | | SPACING TO BE USED. | | 2-TRUSS ANCHOR SCHEDULE WAS REVISED ON | | SHEET S-3 BUT NOT ON SHEET S-2. | | 3-REVISED ENERGY CALCULATIONS WERE NOT | | RE-SUBMITTED. (THERE IS NOT ADJACENT | | FRAMING, BUT MASONRY AND OWNER/AGENT | | TO DATE BOTTOM OF FORM AS WELL). |
|