Plan Review Notes
Plan Review Notes For Permit 02080494
Permit Number 02080494
Review Stop R
Sequence Number 1
Notes
Date Text
2002-09-17 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS
 SHOWING HOW THE FLOOR & ROOF DIAPHRAGM
 TRANSFER ALL LOADS CONSIDERING THE
 DOUBLE CEILING AREA AND FLOOR WOOD
 COLUMNS SUPPORTS WITH TOP AND BOTTOM
 CONNECTORS THAT DON'T PROVIDE RESIS-
 TANCE TO LATERAL FORCES. SEC. 1606.2.4
 FBC 2001 AND SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS. SEE LIMITATIONS ON
 PRODUCT APPROVAL SUBMITTED.
 4-PROVIDE LEGIBLE PRODUCT APPROVAL FOR
 GARAGE DOORS.
 5-SPECIFY FIREBLOCKING MATERIAL & LOCA-
 TION AT STAIRS. SEE SEC. 2305.1.4 FBC.
 6-PROVIDE GENERAL SPECS FOR REQUIRED
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEC. 2305.1.4 FBC 2001.
 7-SHEET C-1: REVISE FOUNDATION NOTE. USE
 0.006 MIL VISQUEEN. SEC. 1909.2 FBC.
 8-PROVIDE SAFETY GLASS IN WINDOW AT 1ST.
 FLOOR BATHROOM. SEC. 2405.2 FBC 2001.
 9-PROVIDE STRUCTURAL DETAIL FOR RECESSED
 WINDOWS TO ALLOW FOR STORM SHUTTERS
 INSTALLATION. SEE PRODUCT APPROVAL FOR
 REQUIRED ENGINEERING.
 10-24SH WINDOW AT MASTER BEDROOM DOESN'T
 ALLOW 24" MIN. CLEAR HEIGHT AND 5.7S.F
 MIN. CLEAR OPENING. SEC. 1005.4.4 FBC.
 11-REVISE NOTE #1 ON STAIR KEY NOTES.
 HEIGHT OF HANDRAIL TO BE BET. 34" AND
 38" HIGH MAX. SEE SEC. 1007.5.1 FBC.
 12-SHEET A-7: A)SOME INFORMATION IS OVER
 LAPPING. B)NOTE #9: REVISE SIZE OF
 LEDGER. SEE 2ND. FLOOR FRAMING PLAN.
 C)REVISE HANDRAIL HEIGHT ON STAIR
 SECTION AS WELL.
 13-SHEET S-1: A)CLARIFY REINFORCING FOR
 FOOTING F5530. B)LINTEL SCHEDULE DOES
 NOT MATCH PLANS. REVISE AS REQUIRED.
 14-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 15-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP PUBLISHED VALUES OR PROVIDE
 ENGINEERED CALCS FOR DIFFERENT VALUES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 16-SHEET S-2: SECTION 1 AND SECTION 2
 HAVE DIFFERENT SPECS. REVISE AS REQ'D
 17-ROOF SHEATHING & NAILING STATEMENT &
 DIAPHRAGM SCHEDULE HAVE DIFFERENT
 SPECS. CLARIFY/REVISE AS REQUIRED.
 18-IDENTIFY ROOF NAILING ZONES. TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001.
 19-SPECIFY CONNECTORS FOR GIRDER TRUSS
 AT GARAGE ROOF FRAMING PLAN. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 20-REVISE ENERGY CALCULATIONS:
 A)THERE IS NOT ADJACENT FRAMING, BUT
 ADJACENT MASONRY.
 B)OWNER/AGENT TO DATE BOTTOM OF FORM
 WHEN SIGNING IT.
 21-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK REQUIREMENTS & REVISE
 DETAIL AS REQUIRED.
 SPECIFY SIZE OF WASHER. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 22-SHEET S-1: CLARIFY TYP. DETAIL AT
 BOND BEAM ELEVATION CHANGE. IS IT 1#7
 OR 1#5. SEE BB SPECS.SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 23-SHEET A-2: UPDATE PLUMBING NOTE. USE
 FPC 2001.
 24-SPACY SPACING FOR WWM SUPPORTS IN
 CONCRETE SLAB. SEC. 1909.3 FBC 2001.
 25-ROOF FRAMING PLAN: SOME CONNECTORS
 DON'T RESIST THE UPLIFT LOADS THAT
 WERE CALCULATED FOR GIRDER TRUSSES.
 SEE CONNECTORS TC-5 AND TC-6.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.