2002-09-17 00:00:00 | CHECKLIST: |
| 1-PROVIDE ENGINEERING ANALYSIS/CALCS |
| SHOWING HOW THE FLOOR & ROOF DIAPHRAGM |
| TRANSFER ALL LOADS CONSIDERING THE |
| DOUBLE CEILING AREA AND FLOOR WOOD |
| COLUMNS SUPPORTS WITH TOP AND BOTTOM |
| CONNECTORS THAT DON'T PROVIDE RESIS- |
| TANCE TO LATERAL FORCES. SEC. 1606.2.4 |
| FBC 2001 AND SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 3-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS. SEE LIMITATIONS ON |
| PRODUCT APPROVAL SUBMITTED. |
| 4-PROVIDE LEGIBLE PRODUCT APPROVAL FOR |
| GARAGE DOORS. |
| 5-SPECIFY FIREBLOCKING MATERIAL & LOCA- |
| TION AT STAIRS. SEE SEC. 2305.1.4 FBC. |
| 6-PROVIDE GENERAL SPECS FOR REQUIRED |
| FIREBLOCKING AT ALL CONCEALED SPACES. |
| SEC. 2305.1.4 FBC 2001. |
| 7-SHEET C-1: REVISE FOUNDATION NOTE. USE |
| 0.006 MIL VISQUEEN. SEC. 1909.2 FBC. |
| 8-PROVIDE SAFETY GLASS IN WINDOW AT 1ST. |
| FLOOR BATHROOM. SEC. 2405.2 FBC 2001. |
| 9-PROVIDE STRUCTURAL DETAIL FOR RECESSED |
| WINDOWS TO ALLOW FOR STORM SHUTTERS |
| INSTALLATION. SEE PRODUCT APPROVAL FOR |
| REQUIRED ENGINEERING. |
| 10-24SH WINDOW AT MASTER BEDROOM DOESN'T |
| ALLOW 24" MIN. CLEAR HEIGHT AND 5.7S.F |
| MIN. CLEAR OPENING. SEC. 1005.4.4 FBC. |
| 11-REVISE NOTE #1 ON STAIR KEY NOTES. |
| HEIGHT OF HANDRAIL TO BE BET. 34" AND |
| 38" HIGH MAX. SEE SEC. 1007.5.1 FBC. |
| 12-SHEET A-7: A)SOME INFORMATION IS OVER |
| LAPPING. B)NOTE #9: REVISE SIZE OF |
| LEDGER. SEE 2ND. FLOOR FRAMING PLAN. |
| C)REVISE HANDRAIL HEIGHT ON STAIR |
| SECTION AS WELL. |
| 13-SHEET S-1: A)CLARIFY REINFORCING FOR |
| FOOTING F5530. B)LINTEL SCHEDULE DOES |
| NOT MATCH PLANS. REVISE AS REQUIRED. |
| 14-SPECIFY FIRECUT REQUIREMENTS ON THE |
| STRUCTURAL WALL SECTIONS. SEC. 2305.4 |
| 15-REVISE TRUSS CONNECTOR SCHEDULE TO |
| MATCH USP PUBLISHED VALUES OR PROVIDE |
| ENGINEERED CALCS FOR DIFFERENT VALUES. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 16-SHEET S-2: SECTION 1 AND SECTION 2 |
| HAVE DIFFERENT SPECS. REVISE AS REQ'D |
| 17-ROOF SHEATHING & NAILING STATEMENT & |
| DIAPHRAGM SCHEDULE HAVE DIFFERENT |
| SPECS. CLARIFY/REVISE AS REQUIRED. |
| 18-IDENTIFY ROOF NAILING ZONES. TABLE |
| 2306.1 CITY AMENDMENTS TO FBC 2001. |
| 19-SPECIFY CONNECTORS FOR GIRDER TRUSS |
| AT GARAGE ROOF FRAMING PLAN. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 20-REVISE ENERGY CALCULATIONS: |
| A)THERE IS NOT ADJACENT FRAMING, BUT |
| ADJACENT MASONRY. |
| B)OWNER/AGENT TO DATE BOTTOM OF FORM |
| WHEN SIGNING IT. |
| 21-SEE GARAGE DOOR PRODUCT APPROVAL FOR |
| STRUCTURAL BUCK REQUIREMENTS & REVISE |
| DETAIL AS REQUIRED. |
| SPECIFY SIZE OF WASHER. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 22-SHEET S-1: CLARIFY TYP. DETAIL AT |
| BOND BEAM ELEVATION CHANGE. IS IT 1#7 |
| OR 1#5. SEE BB SPECS.SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 23-SHEET A-2: UPDATE PLUMBING NOTE. USE |
| FPC 2001. |
| 24-SPACY SPACING FOR WWM SUPPORTS IN |
| CONCRETE SLAB. SEC. 1909.3 FBC 2001. |
| 25-ROOF FRAMING PLAN: SOME CONNECTORS |
| DON'T RESIST THE UPLIFT LOADS THAT |
| WERE CALCULATED FOR GIRDER TRUSSES. |
| SEE CONNECTORS TC-5 AND TC-6. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |