2002-11-06 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-STORM SHUTTERS: A)DESIGN PRESSURES
 SPECIFIED HAVE LIMITATIONS FOR PANEL
 SPAN. SEE PLANS FOR CALCULATED DESIGN
 PRESSURES AND REVISE AS REQUIRED.
 B)CLARIFY TYPE OF ANCHOR USED. RAWL OR
 CAULK-IN.
 C)MARK ON DWGS THE SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE & SPACING
 TO BE USED.
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SINGLE SIDELITE ASSEMBLY AS
 SHOWN ON PLANS.
 3-PROVIDE COMPLETE UL LISTING AND SPECS
 FOR ONE HOUR FIRE RATED GLASS BLOCK
 ASSEMBLY AS REQUIRED BY TABLE 600 FBC.
 **ALSO, PROVIDE CLEAR & LEGIBLE PRODUCT
 APPROVAL FOR GLASS BLOCK.
 **NOTE: IF GLASS BLOCK FACE THICKNESS IS
 LESS THAN 0.25", THEN SAFETY GLASS IS
 REQUIRED. SEC. 2405.2.2. FBC 2001.
 4-ENERGY CALCULATIONS WERE NOT REVISED.
 REVISE UNDER ATTIC AREA AS REQUIRED BY
 SEC. 602.1.ABC.1.2 OF CHAPTER 13 FBC.
 OWNER/AGENT TO SIGN AND DATE FORM ALSO
 5-FOUNDATION PLAN AND FOOTING SCHEDULE
 DON'T MATCH. REVISE AS REQUIRED.
 **ALSO, FOOTING SCHEDULE & WALL SECTIONS
 DON'T MATCH. SEE DIMENSIONS FOR LENGTH
 AND WIDTH AND REVISE AS REQUIRED.