2002-11-06 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-STORM SHUTTERS: A)DESIGN PRESSURES |
| SPECIFIED HAVE LIMITATIONS FOR PANEL |
| SPAN. SEE PLANS FOR CALCULATED DESIGN |
| PRESSURES AND REVISE AS REQUIRED. |
| B)CLARIFY TYPE OF ANCHOR USED. RAWL OR |
| CAULK-IN. |
| C)MARK ON DWGS THE SPECIFIC MOUNTING |
| CONDITIONS AND ANCHOR TYPE & SPACING |
| TO BE USED. |
| 2-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| DOOR WITH SINGLE SIDELITE ASSEMBLY AS |
| SHOWN ON PLANS. |
| 3-PROVIDE COMPLETE UL LISTING AND SPECS |
| FOR ONE HOUR FIRE RATED GLASS BLOCK |
| ASSEMBLY AS REQUIRED BY TABLE 600 FBC. |
| **ALSO, PROVIDE CLEAR & LEGIBLE PRODUCT |
| APPROVAL FOR GLASS BLOCK. |
| **NOTE: IF GLASS BLOCK FACE THICKNESS IS |
| LESS THAN 0.25", THEN SAFETY GLASS IS |
| REQUIRED. SEC. 2405.2.2. FBC 2001. |
| 4-ENERGY CALCULATIONS WERE NOT REVISED. |
| REVISE UNDER ATTIC AREA AS REQUIRED BY |
| SEC. 602.1.ABC.1.2 OF CHAPTER 13 FBC. |
| OWNER/AGENT TO SIGN AND DATE FORM ALSO |
| 5-FOUNDATION PLAN AND FOOTING SCHEDULE |
| DON'T MATCH. REVISE AS REQUIRED. |
| **ALSO, FOOTING SCHEDULE & WALL SECTIONS |
| DON'T MATCH. SEE DIMENSIONS FOR LENGTH |
| AND WIDTH AND REVISE AS REQUIRED. |