2002-09-18 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS AND
 COMPLETE SECTIONS/DETAILS/SPECS FOR
 DESIGN OF GABLE END AT FRONT ELEVATION
 CONSIDERING THAT CENTER OF GABLE END @
 FRONT ELEVATION IS MASONRY AND THE TWO
 SIDES ARE PARTIAL GABLE END TRUSSES.
 CLARIFY HOW IS GABLE END WALL PUT
 TOGETHER TO TRANSFER THE LOADS. SEE
 SECTIONS 1604.2.4, 2105, 2107, 2117 &
 2313 FBC 2001.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-REVISE ATTIC ACCESS SIZE. 36" MIN. NOT
 30". SEC. 2309.6 FBC 2001.
 4-34SH WINDOW DOESN'T PROVIDE 24" MIN.
 CLEAR OPENING HEIGHT. SEC. 1005.4.4.
 5-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS. SEE PRODUCT APPRO-
 VAL FOR LIMITATIONS.
 6-PROVIDE PRODUCT APPROVAL FOR SINGLE
 ENTRY DOOR WITH SINGLE SIDELITE AS
 SHOWN ON PLANS.
 7-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR ONE HR FIRE RATED GLASS BLOCK
 ASSEMBLY REQUIRED BY TABLE 600 FBC.
 **NOTE: GLASS BLOCK TO BE SAFETY GLASS
 IF UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2.2 FBC 2001.
 8-REVISE GLASS BLOCK ASSEMBLY DETAIL TO
 MATCH UL SPECIFICATIONS SUBMITTED.
 **REVISE WINDOW SCHEDULE: SPECIFY REQ'D
 1 HR FIRE RATED GLASS BLOCK.
  
 9-SPECIFY SPACING FOR SUPPORTS OF WWM
 IN CONCRETE SLAB. SEC. 1909.3 FBC 2001
 10-PROVIDE COMPLETE DETAIL AT RECESSED
 WINDOWS TO ALLOW FOR STORM SHUTTERS
 INSTALLATION. SEE STORM SHUTTERS
 PRODUCT APPROVAL FOR LIMITATIONS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 11-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA. SEE SECTION
 602.1.ABC.1.2 CHAPTER 13 FBC 2001.
 B)OWNER/AGENT TO DATE BOTTOM OF FORM
 WHEN SIGNING IT.
 12-WALL SECTIONS NOTE #14 AND VENT CALCS
 DON'T MATCH. REVISE AS REQUIRED.
 13-SHEET S-2:A) UPDATE NOTE #2: SEMCO
 CONNECTOR.
 B)UPDATE NOTE #3: REFER TO FBC 2001 FOR
 140 MPH, NOT ASCE 7-93.
 C)CLARIFY WHY BLOCKING AT FRONT END IS
 SHOWN ON PARTIAL GABLE END AND NOT ALL
 THE WAY DOWN TO THE ENDS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 14-SHEET S-1: A) CLARIFY DIMENSION OF
 4'-1 1/2" ON SECTION 5.
 B)PROVIDE INSTALLATION DETAIL FOR LINTEL
 L-7 AT FRONT PORCH. LINTEL IS NOT
 RESTING ON MASONRY COLUMN FOR CONTI-
 NUOUS VERTICAL REINFORCEMENT. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)REVISE LINTEL SCHEDULE TO MATCH PLANS.
 CHECK SIZES AND LINTEL SPECIFIED.
  
 15-IDENTIFY ROOF ZONES ON ROOF FRAMING
 PLAN. TABLE 2306.1 CITY AMENDMENTS.
 16-REVISE TRUSS ANCHOR SCHEDULE TO MATCH
 USP PUBLISHED VALUES. PROVIDE ENGI-
 NEERING CALCS FOR DIFFERENT VALUES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 17-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 STRUCTURAL BUCK REQUIREMENTS. REVISE
 DETAIL AS REQUIRED.
 **SPECIFY WASHER.
 18-UPDATE FOUNDATION NOTE ON SHEET C-1:
 NEED 0.006 MIL VISQUEEN MIN. SECTION
 1909.2 FBC 2001.
 19-REVIEW ALL FLOOR PLANS AND CLEARLY
 KEY DETAILS AND SECTIONS THAT MATCH
 SHEET THEY ARE REFERENCING TO.
 20-UPDATE GENERAL NOTE ON SHEET A-1:
 REFER TO FPC 2001, NOT SPC 1994.
 21-SHEET A-3: REVISE SECTION THRU ENTRY
 TO MATCH MASONRY CONSTRUCTION.
 SEC. 2117 FBC 2001.