2002-10-22 00:00:00 | APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS UNDER A SEPARATE |
| PERMIT. NEED SITE SPECIFIC CONDITIONS |
| USING THE CERTIFICATE OF COMPLIANCE |
| METHOD AND INSTALLATION AFFIDAVIT. SEE |
| CITY IMPLEMENTATION STANDARD FOR HURRI |
| CANE MISSILE IMPACT PROTECTION. |
| **SEE GENERAL NOTES ON PAGE 1 OF STORM |
| SHUTTERS DRAWINGS FOR ADDITIONAL LIMI- |
| TATIONS FOR THIS STORM SHUTTERS. |
| 2-PROVIDE SOIL TEST REPORT. |
| 3-FLOOD ZONE A8. NEED TO PROVIDE THE |
| ELEVATION CERTIFICATE. |
| 4-GLASS BLOCK: |
| A)PRODUCT APPROVAL IS NOT LEGIBLE. |
| B)PROVIDE COMPLETE UL SPECS FOR ONE HR |
| FIRE RATED GLASS BLOCK ASSEMBLY. |
| C)REVISE GLASS BLOCK DETAIL TO MATCH ONE |
| HOUR FIRE RATED ASSEMBLY. SEE UL SPECS |
| D)PROVIDE INFORMATION STATING THE FACE |
| THICKNESS OF GLASS. NEED SAFETY GLASS |
| IF FACE THICKNESS IS LESS THAN 0.25". |
| SEC. 2405.2.2 FBC 2001. |
| 5-ENTRY DOOR PRODUCT APPROVAL REPORT IS |
| MISSING SOME PAGES. RESUBMIT AS REQ'D. |
| 6-PROVIDE ENGINEERED CALCULATIONS FOR 1" |
| WASHER USED AT GARAGE STRUCTURAL BUCK. |
| NOTE: CONSIDER WOOD USED & REDUCTION |
| FACTOR FOR P.T. WOOD. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |