2002-09-23 00:00:00 | CHECKLIST: |
| 1-FLOOD ZONE A8. WILL NEED ELEVATION |
| CERTIFICATE. |
| 2-PROVIDE SOIL TEST REPORT. |
| 3-NEED RECORDED N.O.C. |
| 4-SHEET C-1: UPDATE FOUNDATION NOTE. |
| NEED 0.006 MIL VISQUEEN. SEC. 1909.2 |
| 5-SHEET A-2: A)REVISE WINDOW SCHEDULE. |
| 24SH AND 34SH WINDOWS DON'T ALLOW THE |
| 24" MIN. CLEAR HEIGHT OPENING AND THE |
| 5.7 S.F. MIN. TOTAL CLEAR OPENING. |
| SEC. 1005.4.4 FBC 2001. |
| B)GLASS BLOCK TO BE 1 HR FIRE RATED |
| ASSEMBLY. TABLE 600 FBC 2001. |
| **NOTE A): SEE PRODUCT APPROVAL AND UL |
| SPECS SUBMITTED BY CONTRACTOR & REVISE |
| DETAIL AS REQUIRED. ALSO, NOTE THAT |
| GLASS BLOCK SUBMITTED IS NOT BY P.C. |
| **NOTE B)GLASS BLOCK TO BE SAFETY GLASS |
| IF UNIFORM FACE THICKNESS IS LESS THAN |
| 0.25".SEC. 2405.2 FBC 2001. |
| C)UPDATE PLUMBING INFORMATION ON NOTE #6 |
| 6-SHEET A-4: A)REVISE STAIR KEY NOTE #1. |
| HANDRAIL HEIGHT TO BE BET. 34" AND 38" |
| SEE SEC. 1007.5.1 FBC 2001. |
| B)NOTE #14: SPEC. FIREBLOCKING MATERIAL. |
| (FIREBLOCKING AND DRAFSTOPPING ARE NOT |
| THE SAME THING. REVISE NOTE AS REQ'D) |
| **NOTE: SEE SEC. 2305.1.4 FOR LOCATIONS |
| TO HAVE FIREBLOCKING AT STAIRS. |
| ALSO, SEE SEC. 2305.1.2 FBC 2001. |
| C)PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| AT ALL CONCEALED AREAS AS REQUIRED BY |
| SEC. 2305.1.4 FBC 2001. |
| 7-NOTE #14: VENT SIZE DOESN'T MATCH VENT |
| CALCULATIONS. REVISE AS REQUIRED. |
| 8-SHEET S-1: A) SPECIFY SPACING FOR WWM |
| SUPPORTS IN CONCRETE SLAB. SEC. 1909.3 |
| B)CLARIFY SIZE OF BUCKET SHOWN ON DETAIL |
| S6. SEE SIZE OF GIRDER TRUSS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| C)DETAIL S21 DOESN'T MATCH CONDITIONS ON |
| PLAN. PROVIDE DETAIL SHOWING ACTUAL |
| CORNER CONDITION. SEC. 104.2.1.2 CITY |
| D)CLARIFY WHY SOME TRUSS GIRDERS ON 2ND |
| FLOOR PLAN ARE NOT RESTING ON COLUMNS. |
| SEE PLAN. |
| E)SPECIFY UPLIFT LOADS ON ROOF FRAMING |
| PLAN AND KEY PROPER ANCHOR. SECTION |
| 104.2.1.2 CITY AMENDMENTS AND CHAPTER |
| 16 FBC 2001. |
| F)SHOWNAILING ZONES IN ROOF PLAN. SEE |
| TABLE 2306.1 CITY AMENDMENTS TO FBC. |
| 9-REVISE TRUSS ANCHOR SCHEDULE TO MATCH |
| USP PUBLISHED VALUES. PROVIDE ENGINEE- |
| RING CALCS FOR DIFFERENT VALUES. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 10-SHEET S-3: A)PROVIDE FIRECUT SPECS IN |
| WALL SECTIONS. SEC. 2305.4 FBC 2001. |
| B)SECTION S2 HAS SOME INFORMATION OVER- |
| LAPPING. REVISE AS REQUIRED. |
| C)DETAIL F14: SPECIFY HOW LONG ARE THE |
| ANCHOR BOLTS. SEC. 104.2.1.2 CITY |
| 11-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| FRAMED OPENING TO RECEIVE ARCHED WIND. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 12-PROVIDE COMPLETE/CORRECT INFORMATION |
| FOR STORM SHUTTERS. |
| 13-PROVIDE PRODUCT APPROVAL FOR: ENTRY |
| DOOR, SINGLE HUNG WINDOW, FIXED WINDOW |
| WINDOW MULLIONS, SLIDING GLASS DOORS |
| AND GARAGE DOORS WITH LEGIBLE DRAWINGS |
| |
| NOTE: SEE REVIEWED SET OF PLANS FOR |
| REFERENCE AND PLEASE RETURN THEM |
| AFTER CORRECTIONS ARE DONE TO THE |
| ORIGINAL DRAWINGS IN ORDER TO |
| EXPEDITE THE REVIEW PROCESS. |
| THANK YOU. |