Plan Review Notes For Permit 02080362 |
Permit Number |
02080362 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-10-28 00:00:00 | APPROVED WITH PROVISO: | | 1-STRUCTURAL PLANS TO MATCH ENGINEER'S | | CALCULATIONS. SEE ENGINEER'S REPORT | | FOR SIZE OF FASTENERS USED FOR SHEAR | | CALCULATIONS. | | 2-CLARIFY SIZE OF FOOTING. SEE FOOTING | | SCHEDULE AND ALL WALL SECTIONS. THE DO | | NOT MATCH. | | 3-PROVIDE PRODUCT APPROVAL FOR EXTERIOR | | SWING SIDE DOOR AT GARAGE. | | 4-REVISE STORM SHUTTERS INSTALLATION | | SCHEDULE: A)CLARIFY DESIGN PRESSURES. | | SEE ARCHITECTURAL DWGS. B)CLARIFY | | TYPE OF ANCHOR TO BE USED: RAWL OR | | CAULK-IN. C)MARK ANCHOR TYPE & SPACING | | SPACING ON STORM SHUTTERS INSTALLATION | | SCHEDULE OF STORM SHUTTERS DRAWINGS. |
|