Date Text
2002-09-06 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-A)SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION @ STAIRS. INCLUDING TOP OF
 STAIRS. SEE SEC. 2305.1.4 FBC 2001.
 B)PROVIDE GENERAL SPECS FOR REQUIRED
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEE SEC. 2305.1.4 FBC 2001.
 3-DRAFSTOPPING TO BE LOCATED FOR AREAS
 NOT TO EXCEED 500 S.F. REVISE AS REQ'D
 SEE SEC. 2305.2.2 FBC 2001.
 4-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEE SEC.
 2305.4 FBC 2001.
 5-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC.
 6-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR A
 SEPARATE PERMIT. CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION
 7-PROVIDE UPDATED PRODUCT APPROVALS FOR
 ALL EXTERIOR DOORS, WINDOWS AND WINDOW
 MULLIONS TO BE USED.
 8-REVISE STAIR KEY NOTE #1. HEIGHT OF
 STAIR HANDRAIL TO BE BET. 34" AND 38".
 SEE SECTION 1007.5.1 FBC 2001.
 9-2ND FLOOR FRAMING PLAN:
 PROVIDE DETAIL SHOWING HOW DOES USP
 HL210 WHICH IS A LIGHT GAUGE PURLING
 HANGER IS USED TO HOLD GIRDER TRUSSES.
 10-SECTION 4/S3 IS CALLED 5/S3 ON ROOF
 FRAMING PLAN. CLARIFY/REVISE AS REQ'D.
 11-REVISE DETAIL 4/S3 TO SHOW GABLE
 END. ***NOTE: GABLE END TO BE DESIGNED
 AS PER SEC. 2117 FBC 2001. PROVIDE
 DETAIL WITH COMPLETE SPECS AND SPECIFY
 ALL FASTENERS.
 12-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP PUBLISHED LOADS.
 **NOTE: PROVIDE ENGINEERING CALCS FOR
 LOADS OTHER THAN THE ONES SPECIFIED ON
 USP.
 **REMAINDER: 10D NAILS NEED 1 3/4" MIN.
 PENETRATION TO GET FULL VALUE.
 DON'T MISMATCH NAIL SIZE & LOADS.
 13-THERE IS NOT CONNECTOR SPECIFIED FOR
 ROOF TRUSS WITH CALCULATED UPLIFT LOAD
 OF 2537#.
 14-CONNECTOR T-5 DOESN'T RESIST THE
 UPLIFT LOAD OF 2369# CALCULATED FOR
 THE ROOF GIRDER TRUSS. REVISE AS REQ'D
 15-ROOF SHEATHING & NAILING NOTE ON DWG
 S3 AND SECTION 4/S3 AND DIAPHRAGM
 SCHEDULE HAVE DIFFERENT SPECS. REVISE/
 CLARIFY AS REQUIRED.
 **NOTE: KEEP IN MIND THAT MEAN ROOF HT
 BET. 25' AND 35' REQUIRES 8D RING
 SHANK NAILS MIN. SEE TABLE 2306.1 CITY
 AMENDMENTS TO FBC 2001.
 16-IDENTIFY NAILING ZONES IN ROOF FRAM'G
 PLAN. TABLE 2306.1 CITY AMENDMENTS.
 17-DESIGN PRESSURES FOR ENTRY DOORS ARE
 DIFFERENT ON THE FLOOR PLAN AND EXT.
 ELEVATION. REVISE AS REQUIRED.
 18-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK SPECS & REVISE DETAIL
 AS REQUIRED.
 **NOTE: SPECIFY SIZE OF WASHERS.
 19-PROVIDE STRUCTURAL BUCK DETAIL FOR
 INSTALLATION OF DOUBLE 2X BUCK TO
 ACCOMMODATE THE ENTRY DOORS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 20-UPDATE DRAWING C-1. FOUNDATION NOTE
 STILL CALLS FOR 0.004 MIL VISQUEEN.
 NEED 0.006 MIL. SEC. 1909.2 FBC 2001.
 21-UPDATE NOTE #3 ON SHEET S3. REFERENCE
 FBC 2001 OR ASCE 7-98, NOT ASCE 7-93.
 22-SHEET A4: EXTERIOR ELEVATIONS ARE NOT
 SHOWN AT 1/4" SCALE. REVISE AS REQ'D.
 23-SHEET A-2: UPDATE PLUMBING NOTE #6.
 REFERENCE FPC 2001, NOT SPC 1994.
 24-SHEET A-7: A)SECT'NA/A6 TO BE SEC.
 A/A7. REVISE AS REQUIRED
 B)SPECIFY FIREBLOCKING ON SECTION A/A7.
 SEC. 2305.1.4 FBC 2001.