Plan Review Notes For Permit 02080347 |
Permit Number |
02080347 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-28 00:00:00 | PROVISO:MECHANICAL PERMIT 02080442 | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | AREA BEING VENTILATED) OR TABLE 403.3 | | FOR MECHANICAL VENTILATION. | | | | PROVIDE INFORMATION ON THE DRYER VENT. | | SHOULD DEVELOPED LENGTH BE GREATER THAN | | 25 FT, PROVIDE MANUFACTURER SUBMITTAL | | INSTALLATION DETAILS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|