2002-08-15 00:00:00DENIED:MECHANICAL PERMIT 02080385
  
 ENERGY CALCS INDICATE 12 SEER & PLANS RE
 FLECT 11 SEER.PLEASE CORRELATE.
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  