Plan Review Notes
Plan Review Notes For Permit 02080229
Permit Number 02080229
Review Stop P
Sequence Number 2
Notes
Date Text
2002-09-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. SEC 909.1
 ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. - THE LAUN-
 DRY TRAY SHALL BE TIED IN DOWNSTREAM OF
 THE VENT LINE FOR THE WATER CLOSET. SEE
 RED LINE ON SHEET 1 SUBMITTED.
 2) SANITARY RISER DIAGRAM SHALL REFLECT
 THE FLOOR PLAN. IF THE BLDG DRAIN IS
 ENTERING THE BLDG FROM THE FRONT THEN
 THE MASTER BATH SHALL BE SHOWN ON THE
 RIGHT SIDE OF THE BLDG DRAIN AND BATH
 #2 ON THE LEFT SIDE OF THE BLDG DRAIN
 TO REFLECT THE FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377