2002-08-26 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED TOP WINDOW SHOWN ON REAR
 ELEVATION.
  
 2) THE ROOF FRAMING PLAN ON SHEET 3B
 DOES NOT INDICATE ANY TRUSS ANCHORS OR
 UPLIFTS. THE ANCHOR SCHEDULE INDICATES
 THAT ALL TRUSSES ARE TO BE ANCHORED TO
 THE CONCRETE BEAM WITH ONE SIMPSON HETAL
 OR USP TA/R AND UPLIFT IS LISTED AS
 1383#. IF THE UPLIFT GIVEN ON THE TRUSS
 DRAWINGS EXCEEDS 1383#, A REVISED ROOF
 FRAMING PLAN WILL BE REQUIRED TO BE
 SUBMITTED FOR APPROVAL.