Plan Review Notes For Permit 02080229 |
Permit Number |
02080229 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-26 00:00:00 | ************BUILDING PROVISO************ | | | | 1)PROVIDE (2) CURRENT AND COMPLETE | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | APPROVALS FOR: | | - ARCHED TOP WINDOW SHOWN ON REAR | | ELEVATION. | | | | 2) THE ROOF FRAMING PLAN ON SHEET 3B | | DOES NOT INDICATE ANY TRUSS ANCHORS OR | | UPLIFTS. THE ANCHOR SCHEDULE INDICATES | | THAT ALL TRUSSES ARE TO BE ANCHORED TO | | THE CONCRETE BEAM WITH ONE SIMPSON HETAL | | OR USP TA/R AND UPLIFT IS LISTED AS | | 1383#. IF THE UPLIFT GIVEN ON THE TRUSS | | DRAWINGS EXCEEDS 1383#, A REVISED ROOF | | FRAMING PLAN WILL BE REQUIRED TO BE | | SUBMITTED FOR APPROVAL. |
|