Plan Review Notes For Permit 02080220 |
Permit Number |
02080220 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-26 00:00:00 | ************BUILDING PROVISO************ | | | | 1)PROVIDE (2) CURRENT AND COMPLETE | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | APPROVALS FOR: | | - ARCHED TOP FIXED GLASS WINDOW AS SHOWN | | ON REAR ELEVATION | | | | 2) STRUCTURE IS LOCATED IN AN AO FLOOD | | ZONE AN ELEVATION CERTIFICATE IS | | REQUIRED. | | | | 3) NO ANCHORS OR UPLIFTS ARE INDICATED | | ON THE ROOF FRAMING PLAN ON SHEET 3B. | | THE ANCHOR SCHEDULE STATES THAT SPECIFIC | | ANCHORS ARE TO BE USED UNLESS OTHERWISE | | NOTED ON THE FRAMING PLAN. IF THE TRUSS | | DRAWINGS INDICATE HIGHER VALUES THAN | | LISTED, A REVISED ROOF FRAMING PLAN WILL | | BE REQUIRED. |
|