Plan Review Notes
Plan Review Notes For Permit 02080187
Permit Number 02080187
Review Stop R
Sequence Number 1
Notes
Date Text
2002-08-27 00:00:00************BUILDING PROVISO************
  
 1) STRUCTURE IS LOCATED IN AN 'AO' FLOOD
 ZONE, AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR ARCHED TOP FIXED GLASS
 WINDOW AS SHOWN ON THE REAR ELEVATION.
  
 3) NO UPLIFT VALUES OR CONNECTORS ARE
 INDICATED ON THE ROOF FRAMING PLAN ON
 SHEET 3. THE NOTE ON THE ANCHOR SCHEDULE
 SPECIFIES THE ANCHORS TO BE USED UNLESS
 OTHERWISE NOTED ON FRAMING PLAN. IF THE
 VALUES GIVEN ON THE TRUSS DRAWINGS
 EXCEED THOSE LISTED IN THE ANCHOR
 SCHEDULE A REVISED FRAMING PLAN WILL BE
 REQUIRED TO BE SUBMITTED FOR REVIEW.