Plan Review Notes
Plan Review Notes For Permit 02080162
Permit Number 02080162
Review Stop R
Sequence Number 1
Notes
Date Text
2002-08-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) THE SURVEY SHOWS THE A/C PAD AND
 CONDENSING UNIT LOCATED IN A DRAINAGE
 EASEMENT. AN EASEMENT RELEASE IS
 REQUIRED OR A REVISED SURVEY SHOWING
 RELOCATED EQUIPMENT.
  
 3) PROVIDE DETAIL INDICATING HOW A/C
 EQUIPMENT IS TO SUSPENDED FROM TRUSSES.
 THIS INFORMATION IS ALSO TO BE PROVIDED
 TO THE TRUSS ENGINEER.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED TOP FIXED GLASS WINDOW SHOWN ON
 PLANS AT BEDROOM #3.
 - STORM PANELS (PRODUCT APPROVAL WAS NOT
 WITH KEY PLAN AND INSTALLATION SCHEDULE)
  
 5) NO UPLIFT VALUES OR ANCHORS ARE
 SPECIFIED ON THE ROOF FRAMING PLAN ON
 3A. THE ANCHORAGE SCHEDULE ON 3A NOTES
 THAT CONNECTOR B OR F BE USED UNLESS
 OTHERWISE NOTED ON FRAMING PLAN. PLEASE
 CLARIFY IF THESE CONNECTORS WILL BE
 ADEQUATE TO RESIST ALL LOADS.
  
 6) THE LINTEL OVER THE SLIDING GLASS
 DOOR AT THE LIVING ROOM IS NOT SHOWN ON
 THE ROOFING PLAN ON 3A. PLEASE PROVIDE
 A PRECAST LINTEL SCHEDULE FOR THE TWO
 LINTELS ON PLANS.
  
 7) THE COVERED ENTRY DETAIL ON 3A SHOWS
 THE TRUSSES SITTING ON THE CONCRETE TIE
 BEAM BETWEEN THE 2X8 PLATES. ARE THE
 PLATES CONTINOUS WITH THE TRUSSES
 SITTING ON TOP OF THEM. PLEASE CLARIFY.
  
 8) PROVIDE A DETAIL OF THE INTERIOR WOOD
 FRAME BEARING WALLS. INDICATE ANCHORS,
 CONNECTORS,ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202