Plan Review Notes
Plan Review Notes For Permit 02080135
Permit Number 02080135
Review Stop FS
Sequence Number 1
Notes
Date Text
2002-08-01 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL, MECHANICAL, AND SERVICE
 TYPE ROOMS.
  
 2) THE FDV'S LOCATED BETWEEN 7 AND 8
 ON PAGES 2 AND 3 COULD POSSIBLY BE
 BLOCKED BY PARKED VEHICLES. PLEASE
 ADVISE AND REVISE AS REQUIRED.
  
 3) ALL EXTERIOR FIRE SPRINKLER HEADS
 ARE TO BE CORROSION RESISTANT.
  
 4) IT IS BELIEVED THAT EXISTING FIRE
 SPRINKLER HEADS BELOW THE CANOPY WAS
 DEMOLISHED RECENTLY. THIS OFFICE WAS
 ADVISED THAT NEW FIRE SPRINKLER HEADS
 WOULD BE INSTALLED TO MATCH EXISTING
 PROTECTION. SOME PROTECTION IS SHOWN
 BUT IS IT IDENTICAL TO WHAT WAS THERE
 PREVIOUSLY. ARE THE SIDEWALL HEADS SHOWN
 ON PAGE 4 AT THE PROPER ELEVATION TO
 SERVE THIS PURPOSE.
  
 5) ARE ANY ROOF MANIFOLDS BEING
 PROVIDED.
  
 6) PLANS INDICATE FIRE SPRINKLER DESIGN
 IS IN ACCORDANCE WITH NFPA 13, 2000
 EDITION. SHOULD READ 1999 EDITION.
  
 7) PLEASE PROVIDE VERTICAL DETAILS OF
 STANDPIPE SYSTEMS AND ANY VERTICAL
 SHAFTS THAT REQUIRE FIRE SPRINKLER
 PROTECTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910