Plan Review Notes For Permit 02080111 |
Permit Number |
02080111 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-08-15 00:00:00 | PROVISO:MECHANICAL PERMIT 02080168 | | | | 2ND FLOOR AHU CLOSET SHALL NOT BE USED | | FOR STORAGE AS NOT TO BLOCK RETURN AIR. | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE | | AREATO THE OUTDOORS. (4 PERCENT OF THE | | FLOOR AREA BEING VENTILATED) OR TABLE | | 403.3 FOR MECHANICAL VENTILATION. | | | | WHERE MULTIPLE AIR-HANDLING SYSTEMS | | SHARE COMMON SUPPLY OR RETURN AIR DUCTS | | OR PLENUMS WITH A COMBINED DESIGN | | CAPACITY GREATER THAN 2,000 CFM, THE | | RETURN AIR & SUPPLY SYSTEM SHALL BE | | PROVIDED WITH SMOKE DETECTORS IN | | ACCORDANCE WITH SECTION 602.1 OR UPON | | ACTIVATION, THE SMOKE DETECTORS SHALL | | SHUT DOWN THE AIR DISTRIBUTION SYSTEM | | 2001 FBC(M) 606.2.2 & 606.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|