Plan Review Notes
Plan Review Notes For Permit 02080109
Permit Number 02080109
Review Stop M
Sequence Number 1
Notes
Date Text
2002-08-15 00:00:00PROVISO:MECHANICAL PERMIT 02080172
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 WHERE MULTIPLE AIR-HANDLING SYSTEMS
 SHARE COMMON SUPPLY OR RETURN AIR DUCTS
 OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM, THE
 RETURN AIR & SUPPLY SYSTEM SHALL BE
 PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH SECTION 602.1 OR UPON
 ACTIVATION, THE SMOKE DETECTORS SHALL
 SHUT DOWN THE AIR DISTRUBUTION SYSTEM
 2001 FBC(M) 606.2.2 & 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.