Plan Review Notes For Permit 02071914 |
Permit Number |
02071914 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-07-31 00:00:00 | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | AIR (JUMPER). | | | | ATTIC ACCESS OPENING SHALL BE NO LESS | | THAN 30" X 22" AS PER 2001 FBC(M) 306.3 | | | | 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 - | | 1. THE SERVICE PANEL OF THE EQUIPMENT IS | | LOCATED WITHIN 6 FT OF AN ATTIC | | ACCESS. | | 2. A DEVICE IS INSTALLED TO ALERT THE | | OWNER OR SHUT DOWN WHEN THE | | CONDENSATE DRAIN IS NOT WORKING | | PROPERLY. | | 4. A NOTICE IS POSTED ON THE ELECTRIC | | SERVICE PANEL INDICATING TO THE | | HOMEOWNER THAT THE AIR HANDLER IS | | LOCATED IN THE ATTIC. | | | | OVERFLOW PROTECTION REQUIRED AS PER | | 2001 FBC(M) 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|