Plan Review Notes For Permit 02071908 |
Permit Number |
02071908 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-07-31 00:00:00 | PROVISO: | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | AIR (JUMPER). | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|