2002-08-07 00:00:00SHEET C2.WHERE WILL THE CONDUIT/COAX
 TERMINATE?WILL IT BE INTERIOR OR
 EXTERIOR TO THE BUILDING?MULTIPLE
 FLOOR PENETRATIONS?
  
 SHEET C5. FBC 705.6.1.2 REQUIRES THE
 FIRE STOP SYSTEM TO HAVE A T RATING OF
 ONE HOUR FOR ROOF PENETRATION AND TWO
 HOURS FOR FLOOR PENETRATION IN TYPE I
 AND II CONSTRUCTION.THE ASSEMBLY
 SHOWN DECLARES A MAXIMUM OF 3/4 HOUR.
 PLEASE REVISE AS NECESSARY.
  
 SHEET S1.ANTENNAS AND THEIR
 CONNECTION ARE NOT DETAILED.IF THE
 WORK IS NOT SHOWN ON THE PLANS A
 SEPARATE PERMIT, PLANS, ENGINEERING AND
 FEES WILL BE REQUIRED.SEE FBC 104.1.3.