Notes |
Date |
Text |
2002-08-07 00:00:00 | SHEET C2.WHERE WILL THE CONDUIT/COAX | | TERMINATE?WILL IT BE INTERIOR OR | | EXTERIOR TO THE BUILDING?MULTIPLE | | FLOOR PENETRATIONS? | | | | SHEET C5. FBC 705.6.1.2 REQUIRES THE | | FIRE STOP SYSTEM TO HAVE A T RATING OF | | ONE HOUR FOR ROOF PENETRATION AND TWO | | HOURS FOR FLOOR PENETRATION IN TYPE I | | AND II CONSTRUCTION.THE ASSEMBLY | | SHOWN DECLARES A MAXIMUM OF 3/4 HOUR. | | PLEASE REVISE AS NECESSARY. | | | | SHEET S1.ANTENNAS AND THEIR | | CONNECTION ARE NOT DETAILED.IF THE | | WORK IS NOT SHOWN ON THE PLANS A | | SEPARATE PERMIT, PLANS, ENGINEERING AND | | FEES WILL BE REQUIRED.SEE FBC 104.1.3. |
|