Plan Review Notes For Permit 02071681 |
Permit Number |
02071681 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-08-02 00:00:00 | *************** UNSAT **************** | | | | PLEASE NOTE THAT AS PER FEILD INSPECTION | | VALUE OF JOB EXCEEDS SUBMITTED APPLIED | | VALUE. | | PLEASE ALSO NOTE THAT A CORRECTION | | NOTICE WAS ISSUED FOR ELECTRICAL DEMO | | AND TEMP POWER FOR CONSTRUCTION. | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | FOR THE ENTIRE SERVICE AND A BREAK | | DOWN ON EACH "MAINS" LOAD. SHOW EXISTING | | SERVICE ENTRANCE CONDUCTORS, SIZE AND | | TYPE. PLEASE NOTE THAT PER FIELD | | INSPECTION, CONDUCTOR AT POINT OF | | SERVICE HAS INSULATION DETERIORATING. | | PLEASE NOTE EXTENT OF WORK IN BLDG HAS | | FAR EXCEEDED ANY % FOR BRINGING UP TO | | CODE. PLEASE NOTE THAT SERVICE HAS | | MORETHAN 8' OF UNPROTECTED CONDUCTORS | | INSIDE THE BLDG.230-70 | | PLEASE NOTE THAT MAIN ELECTRICAL ROOM | | NEEDS TO BE LOCKED AND ONLY OPENED FOR | | QUALIFIED PERSONNEL. PLEASE NOTE FIRE | | RATING FOR MAIN ELECTRICAL ROOM TO BE | | 1 HR RATING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|