2002-08-02 00:00:00*************** UNSAT ****************
  
 PLEASE NOTE THAT AS PER FEILD INSPECTION
 VALUE OF JOB EXCEEDS SUBMITTED APPLIED
 VALUE.
 PLEASE ALSO NOTE THAT A CORRECTION
 NOTICE WAS ISSUED FOR ELECTRICAL DEMO
 AND TEMP POWER FOR CONSTRUCTION.
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR THE ENTIRE SERVICE AND A BREAK
 DOWN ON EACH "MAINS" LOAD. SHOW EXISTING
 SERVICE ENTRANCE CONDUCTORS, SIZE AND
 TYPE. PLEASE NOTE THAT PER FIELD
 INSPECTION, CONDUCTOR AT POINT OF
 SERVICE HAS INSULATION DETERIORATING.
 PLEASE NOTE EXTENT OF WORK IN BLDG HAS
 FAR EXCEEDED ANY % FOR BRINGING UP TO
 CODE. PLEASE NOTE THAT SERVICE HAS
 MORETHAN 8' OF UNPROTECTED CONDUCTORS
 INSIDE THE BLDG.230-70
 PLEASE NOTE THAT MAIN ELECTRICAL ROOM
 NEEDS TO BE LOCKED AND ONLY OPENED FOR
 QUALIFIED PERSONNEL. PLEASE NOTE FIRE
 RATING FOR MAIN ELECTRICAL ROOM TO BE
 1 HR RATING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  