2002-08-07 00:00:00 | A FIRE RATED EXIT ACCESS CORRIDOR IS | | REQUIRED BY FBC 704.2.4 FOR OCCUPANCY B | | >30 OCCUPANTS. PROVIDE THE FIRE DESIGN | | NUMBER FOR THE PARTITIONS AND SHOW THE | | RATED OPENING PROTECTIVES. | | | | SHOW THE FIRE RATED TENANT SEPARATION IN | | ACCORDANCE WITH FBC 704.3.1. | | | | DOORS SHOWN NEAR THE TOILET ROOM | | SWINGING INTO THE CORRIDOR DO NOT | | COMPLY WITH FBC 1012.1.4. | | | | SAFETY GLAZING IS REQUIRED FOR THE | | WINDOWS IN OFFICES 6, 7 AND 8.SEE FBC | | 2405.2.1 #3. | | | | THE $18000.00 DECLARED VALUATION IS TOO | | LOW FOR THIS SCOPE OF WORK.$50000.00 | | IS MORE REALISTIC, PLEASE PAY AN | | ADDITIONAL $710.40 PERMIT FEE TO THE | | CITY. |
|