| BUILDING PLAN REVIEW |
| PERMIT: 02071663 |
| ADD: 802 SOUTHERN BLVD |
| CONT: MHS CONTRACTING INC |
| TEL: (561)586-7063 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| |
| (1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| |
| 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORTS: |
| A) SWING DOORS |
| B) STOREFRONT |
| |
| 3) TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| 4)11-4.1.3(3) GROUND & FLOOR SURFACES |
| ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| ROOMS & SPACES SHALL COMPLY WITH |
| 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| IS RECOMENDED FOR ACCESSIBLE ROUTES |
| AND 0.8 FOR RAMPS. |
| |
| 5) 11-4.1.6(H) IF A PARTICULAR |
| ENTRANCE IS NOT MADE ACCESSIBLE, APPRO- |
| PRIATE ACCESSIBLE SIGNAGE INDICATING THE |
| LOCATION OF THE NEAREST ACCESSIBLE |
| ENTRANCE(S) SHALL BE INSTALLED AT OR |
| NEAR THE INACCESSIBLE ENTRANCE, SUCH |
| THAT A PERSON WITH DISABILITIES WILL |
| NOT BE REQUIRED TO RETRACE THE APPROACH |
| ROUTE FROM THE INNACCESSIBLE ENTRANCE. |
| |
| JIM WITMER |
| BUILDING PLAN REVIEW |