Plan Review Notes
Plan Review Notes For Permit 02071609
Permit Number 02071609
Review Stop P
Sequence Number 3
Notes
Date Text
2002-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW:
 COVER SHEET INDICATES WAREHOUSE AND
 SHOWROOM. PLEASE SHOW SQUARE FOOTAGE FOR
 OFFICE, WAREHOUSE, AND SHOWROOM INDIVID-
 UALLY. PLEASE INDICATE PRODUCT THAT WILL
 BE ON SALES ROOM FLOOR AND WAREHOUSE.
 2) FROM PREVIOUS REVIEW:
 PLEASE SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLE 403.1, AND TABLE
 1003.1 (BLDG. CODE). SHOW NUMBER OF PER-
 SONS REQUIRED FOR EACH OCCUPANCY.
 3) FROM PREVIOUS REVIEW:
 PLEASE SUBMIT DETAILS FOR SHOWERS IN RMS
 #104, 105, & 126. SEE SECTION 11-4.21
 SHOWER STALLS. SHOW COMPLIANCE FOR ALL
 SUBSECTIONS, 4.21.2 SIZE/CLEARANCES,
 4.21.3 SEAT, 4.21.4 GRAB BARS, 4.21.5
 CONTROLS, 4.21.6 SHOWER UNIT, 4.21.7
 CURBS. FIGURES 35(A) OR (B), & FIGURE
 57(A) OR (B). - IF BATHING FACILITIES
 ARE PROVIDED ON A SITE, THEN EACH SUCH
 PUBLIC OR COMMON USE BATHING FACILITY
 SHALL COMPLY WITH 11-4.23. SECTION
 11-4.1.2(6).
 4) SHT 3.2 OF 11, SANITARY RISER DIAGRAM
 FLOOR SINK NOT VENTED, AND SINK IN ROOM
 #106 IS NOT SHOWN ON RISER DIAGRAM.
 5) MANUF. INFO. REQUIRED FOR INSTA HOT
 BEING USED. REQUIRES A LISTING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377