Plan Review Notes For Permit 02071609 |
Permit Number |
02071609 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-11-26 00:00:00 | *************** UNSAT ************* | | | | 1)NOTE: PLEASE NOTE, NOTE FROM FIRST | | TWO REVIEWS WERE NOT MET. | | PLEASE NOTE, NO EQUIPMENT GROUNDING | | METHOD IS SHOWN BETWEEN MAINS/PANELS, | | TRANSFORMERS???? 250-24,250-30,250-122 | | ETC. | | | | 2) PLEASE TAKE OUT OLD SHEETS AND INSERT | | NEW SHEETS FOR TWO COMPLTE SETS FOR | | REVIEW. PLEASE NOTE, ONE OLD SET MAY BE | | SUBMITTED FOR REFERENCE IF NEEDED. | | | | 3)NOTE: PLEASE SEE ATTACHED LETTER PER | | FS. 553.80(2)(B) WITH RESPECT TO DESIGN | | PROFESSIONAL. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. ONCE AGAIN, IF THERE ARE ANY | | QUESTIONS, PLEASE CALL. IF A MEETING | | WOULD BE REQ`D TO GO OVER PLANS, PLEASE | | CALL. | | | | DEWEY PALMER | | ELECTRICAL PAN REVIEW | | 561-659-8096 EXT 8372 |
|