Date |
Text |
2002-11-06 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 11 |
| FBC-2001 PLUMBING |
| |
| 1) COVER SHEET INDICATES WAREHOUSE AND |
| SHOWROOM. PLEASE SHOW SQUARE FOOTAGE FOR |
| OFFICE, WAREHOUSE, AND SHOWROOM INDIVID- |
| UALLY. PLEASE INDICATE PRODUCT THAT WILL |
| BE ON SALES ROOM FLOOR AND WAREHOUSE. |
| 2) RPZ BACKFLOW IS REQUIRED ON WATER |
| SERVICE TO BLDG. |
| 3) PLEASE SUBMIT CALCULATIONS FOR MINIM- |
| UM FACILITIES PER TABLE 403.1, AND TABLE |
| 1003.1 (BLDG CODE). SHOW NUMBER OF PER- |
| SONS REQUIRED FOR EACH OCCUPANCY. |
| 4) WHAT WILL BULL PEN BE USED FOR? |
| 5) PLEASE SUBMIT DETAILS FOR SHOWERS IN |
| #104, 105, & 126. SEE SECTION 11-4.21 |
| SHOWER STALLS. SHOW COMPLIANCE FOR ALL |
| SUBSECTIONS, 4.21.2 SIZE/CLEARANCES, |
| 4.21.3 SEAT, 4.21.4 GRAB BARS, 4.21.5 |
| CONTROLS, 4.21.6 SHOWER UNIT, 4.21.7 |
| CURBS. FIGURS 35(A) OR (B), & FIGURE |
| 57(A) OR (B) |
| 6) SHTS 3.1 OF 11 AND 3.2 OF 11, P/T |
| FROM WATER HEATERS SHALL DRAIN TO A |
| FLOOR SINK. FLOOR DRAIN ARE NOT AN APPRO |
| VED INDIRECT WASTE RECEPTOR. |
| 7) SHT 3.2 OF 11, SANITARY AND WATER |
| RISER DIAGRAMS DO NOT REFLECT THE FLOOR |
| PLAN. URNALS ARE ON WALL BEHIND MOP SINK |
| NOT ON THE OTHER SIDE OF ROOM. W/C'S AND |
| LAVS. MISSING OFF BOTH RISERS. WATER |
| HAMMER ARRESTOR LOCATION SHALL BE NEAR |
| THE FIXTURE IN AN "EFFECTIVE RANGE NOT |
| AT THE TOP OF RISER IN CEILING PER PDI- |
| WH 201 AND MANUFACTURE INSTALLATION IN- |
| STRUCTIONS. WATER HAMMER ARRESTORS ARE |
| REQUIRED PER 604.9. AIR CHAMBERS ARE NOT |
| APPROVED. |
| 8) SHT 3.2 OF 11 WATER RISER DIAGRAM, |
| WATER PIPING TO WATER HEATER BY MOP SINK |
| NOT SHOWN ON RISER. |
| 9) THERMAL EXPANSION CONTROL REQUIRED |
| PER 607.3 AND 607.3.2. PLEASE GIVE DE- |
| TAIL. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |