Plan Review Notes
Plan Review Notes For Permit 02071609
Permit Number 02071609
Review Stop P
Sequence Number 2
Notes
Date Text
2002-11-06 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) COVER SHEET INDICATES WAREHOUSE AND
 SHOWROOM. PLEASE SHOW SQUARE FOOTAGE FOR
 OFFICE, WAREHOUSE, AND SHOWROOM INDIVID-
 UALLY. PLEASE INDICATE PRODUCT THAT WILL
 BE ON SALES ROOM FLOOR AND WAREHOUSE.
 2) RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE TO BLDG.
 3) PLEASE SUBMIT CALCULATIONS FOR MINIM-
 UM FACILITIES PER TABLE 403.1, AND TABLE
 1003.1 (BLDG CODE). SHOW NUMBER OF PER-
 SONS REQUIRED FOR EACH OCCUPANCY.
 4) WHAT WILL BULL PEN BE USED FOR?
 5) PLEASE SUBMIT DETAILS FOR SHOWERS IN
 #104, 105, & 126. SEE SECTION 11-4.21
 SHOWER STALLS. SHOW COMPLIANCE FOR ALL
 SUBSECTIONS, 4.21.2 SIZE/CLEARANCES,
 4.21.3 SEAT, 4.21.4 GRAB BARS, 4.21.5
 CONTROLS, 4.21.6 SHOWER UNIT, 4.21.7
 CURBS. FIGURS 35(A) OR (B), & FIGURE
 57(A) OR (B)
 6) SHTS 3.1 OF 11 AND 3.2 OF 11, P/T
 FROM WATER HEATERS SHALL DRAIN TO A
 FLOOR SINK. FLOOR DRAIN ARE NOT AN APPRO
 VED INDIRECT WASTE RECEPTOR.
 7) SHT 3.2 OF 11, SANITARY AND WATER
 RISER DIAGRAMS DO NOT REFLECT THE FLOOR
 PLAN. URNALS ARE ON WALL BEHIND MOP SINK
 NOT ON THE OTHER SIDE OF ROOM. W/C'S AND
 LAVS. MISSING OFF BOTH RISERS. WATER
 HAMMER ARRESTOR LOCATION SHALL BE NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE NOT
 AT THE TOP OF RISER IN CEILING PER PDI-
 WH 201 AND MANUFACTURE INSTALLATION IN-
 STRUCTIONS. WATER HAMMER ARRESTORS ARE
 REQUIRED PER 604.9. AIR CHAMBERS ARE NOT
 APPROVED.
 8) SHT 3.2 OF 11 WATER RISER DIAGRAM,
 WATER PIPING TO WATER HEATER BY MOP SINK
 NOT SHOWN ON RISER.
 9) THERMAL EXPANSION CONTROL REQUIRED
 PER 607.3 AND 607.3.2. PLEASE GIVE DE-
 TAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377