Plan Review Notes
Plan Review Notes For Permit 02071609
Permit Number 02071609
Review Stop M
Sequence Number 2
Notes
Date Text
2002-10-30 00:00:00DENIED:
  
 1.PLEASE PROVIDE EQUIPMENT SCHEDULE
 ON PLAN.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 3.PLEASE INDICATE DUCT SMOKE DETECTORS
 AS PER 2001 FBC(M) 606.2.1 & 606.2.2
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.