Plan Review Notes For Permit 02071609 |
Permit Number |
02071609 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-10-31 00:00:00 | ************* UNSAT **************** | | | | 1)NOTE: PLEASE NOTE/CLARFIY MISSING | | EQUIPMENT GROUNDIGN CONDUCTORS BETWEEN | | PANELS/MAINS/TRANSFORMERS ETC. 250-142 | | 250-122,250-30 | | | | 2)NOTE: PLEASE NOTE PANEL "B" IS NOT | | SHOWN AS BEING FED FROM ANYWHERE? | | PLEASE SHOW. | | | | 3)NOTE: PLEASE NOTE NO MAIN ON LOAD SIDE | | OF TRANSFORMER INTO PANEL "A". LIGHTING | | AND APPL PANELBOARD.384-16, | | | | 4)NOTE: PLEASE SHOW WHERE GRND IS BEING | | ATTACHED FOR TRANSFORMER. 250-30 | | AND FOR MAIN DISC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT8372 |
|