Date |
Text |
2002-08-12 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 11 |
| FBC-2001 PLUMBING |
| |
| 1) SHT A-1 ROOM 106 PRIVATE BATHROOM, |
| PLEASE SHOW DETAILS FOR SHOWER. BACKING |
| REQUIRED FOR GRAB BARS, AND SEAT FOR |
| SHOWER. CURB TO BE MAX 1/2", CONTROLS |
| SHALL BE WITHIN 38" TO 48" OFF FLOOR, |
| SHOW WHICH WALL CONTROL AND SHOWER HEAD |
| ARE ON. LAV SHALL HAVE A REMOVABLE VANI- |
| TY OR BE CENTERED (2') ON THE 48"X30" |
| CLEAR FLOOR SPACE. (PARALLEL APPROACH) |
| PLEASE PROVIDE DETAILS FOR ADAPTABLE |
| BATHROOM. 11-4.21 & ALL SUBSECTIONS |
| 2) SHT A-1 BOTTLED WATER COOLER SHALL |
| COMPLY WITH ARI-1010. PLEASE PROVIDE |
| MANUF. INFORMATION. |
| 3) SHT A-6.1 SANITARY RISER DIAG. FIX- |
| TURES IN ROOM #114 (HDCP W/C, JANITOR |
| SINK, URNALS, ECT SHALL NOT DRAIN INTO |
| THE VENT FOR THE W/C IN THE FIRST STALL. |
| PLEASE DRAIN THESE FIXTURES DOWNSTREAM |
| OF THE VENT FOR THAT W/C. ALSO CHANGE |
| SHT A-5 FLOOR PLAN. |
| 4) SHT A-6.1 WATER RISER DIAGRAM, WATER |
| HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| FIXTURES IN AN "EFFECTIVE RANGE" NOT AT |
| THE TOP OF DROPS AS SHOWN. PDI-WH 201 |
| AND MANUF. INSTALL. INSTRUCTIONS. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |