2002-08-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 ROOM 106 PRIVATE BATHROOM,
 PLEASE SHOW DETAILS FOR SHOWER. BACKING
 REQUIRED FOR GRAB BARS, AND SEAT FOR
 SHOWER. CURB TO BE MAX 1/2", CONTROLS
 SHALL BE WITHIN 38" TO 48" OFF FLOOR,
 SHOW WHICH WALL CONTROL AND SHOWER HEAD
 ARE ON. LAV SHALL HAVE A REMOVABLE VANI-
 TY OR BE CENTERED (2') ON THE 48"X30"
 CLEAR FLOOR SPACE. (PARALLEL APPROACH)
 PLEASE PROVIDE DETAILS FOR ADAPTABLE
 BATHROOM. 11-4.21 & ALL SUBSECTIONS
 2) SHT A-1 BOTTLED WATER COOLER SHALL
 COMPLY WITH ARI-1010. PLEASE PROVIDE
 MANUF. INFORMATION.
 3) SHT A-6.1 SANITARY RISER DIAG. FIX-
 TURES IN ROOM #114 (HDCP W/C, JANITOR
 SINK, URNALS, ECT SHALL NOT DRAIN INTO
 THE VENT FOR THE W/C IN THE FIRST STALL.
 PLEASE DRAIN THESE FIXTURES DOWNSTREAM
 OF THE VENT FOR THAT W/C. ALSO CHANGE
 SHT A-5 FLOOR PLAN.
 4) SHT A-6.1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 FIXTURES IN AN "EFFECTIVE RANGE" NOT AT
 THE TOP OF DROPS AS SHOWN. PDI-WH 201
 AND MANUF. INSTALL. INSTRUCTIONS.
  